Web Interface OperationEaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 1138. To enable an e-mail address for this account, click the link on the e-mail address under the e-mail Addresscolumn.User-Defined Group DefinitionNOTE Only the Administrator has access to this page.NOTE 1 Some monitoring data do not display for the Switched ePDU user-defined groups.This includes Current, Percent load, Apparent Power, Active Power, and kWh.NOTE 2 You cannot change the state (On, Off, or Reboot) of a group of outlets using theWeb interface for Metered Outlet (MO) ePDUs.NOTE 3 The user-defined group feature is not available for Metered Input (MI) ePDUsbecause there are no measurements or controls on the outlets on that model.Configure an Outlet for a User-Defined Outlet Group1. Access the Web interface and log in.2. Under Settings, select Group Definition. The Group Definition page displays.3. Select one group from the list of groups. (The default is Group x, where x is the outlet number.)4. Either accept the default name in the Name text box or type a new name to identify the new group.5. Select Enable from the drop-down list. (Groups with disabled status are not visible in the ePDU Groupmenu.)6. To assign outlets to this group, select the name of the outlets from the Factory Groups, User-DefinedGroups, or Outlets panel and click the right arrow. The outlets move to the Selected Outlets panel.7. Click Save.8. To ensure that you have configured the outlet groups correctly, select the ePDU Group from menu bar inthe to view the groups list.NOTE Up to 12 groups can be configured. One outlet can only be part of one user-definedgroup. You cannot create an empty group.SystemNOTE The Web interface will not be available as follows:l during firmware upgrades using the Upgrade network management card buttonl during a communications module restart using the Restart network management cardbuttonl during restoration to factory defaults using the Restore factory to default settings buttonSetting General System SettingsNOTE Refresh the Web pages (press F5) to see changes to the general system settings.