Serial Interface OperationEaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 79PDU.Input[1].Statistic[5].Reset.Energy Measure Energy saved at the instant the user resets the stat. Wh ROPDU.Input[1].Statistic[5].Reset.Time Measure Timestamp saved at the instant the user resets the stat. s ROPDU.Input[1].Type Constant List types of PDU Input plugs. - ROPDU.Input[2].ActivePower Measure Active Power Measurement.It's the cumul of 1 or 3 phase measures.dW ROPDU.Input[2].ApparentPower Measure Apparent Power Measurement.It's the cumul of 1 or 3 phase measures.dVA ROPDU.Input[2].ChangedStatus.FrequencyOutOfRange Timestamp s ROPDU.Input[2].Frequency Measure Frequency Measurement. dHz ROPDU.Input[2].Mode Constant Wiring Mode0: Wye Measuring1: Delta Measuring2 : Wye Current and Delta Measuring- ROPDU.Input[2].Phase.Count Constant Number of phase managed by the Input module. - ROPDU.Input[2].Phase[x].ActivePower Measure Active Power Measurement. dW ROPDU.Input[2].Phase[x].ApparentPower HideMeasure Apparent Power Measurement. dVA ROPDU.Input[2].Phase[x].ChangedStatus.OverCurrent Timestamp Timestamp of last changing state of the alarm that has thesame name in the collection PresentStatus.s ROPDU.Input[2].Phase[x].ChangedStatus.OverVoltage Timestamp Timestamp of last changing state of the alarm that has thesame name in the collection PresentStatus.s ROPDU.Input[2].Phase[x].Current Measure Current Measurement. mA ROPDU.Input[2].Phase[x].OverCurrent[1].Threshold Parameter mA RWPDU.Input[2].Phase[x].OverCurrent[3].Threshold Parameter mA RWPDU.Input[2].Phase[x].OverCurrent[4].Threshold Parameter mA RWPDU.Input[2].Phase[x].OverVoltage[1].Threshold Parameter cV RWPDU.Input[2].Phase[x].OverVoltage[2].Threshold Parameter cV RWPDU.Input[2].Phase[x].OverVoltage[3].Threshold Parameter cV RWPDU.Input[2].Phase[x].OverVoltage[4].Threshold Parameter cV RWPDU.Input[2].Phase[x].PeakFactor Measure Crest factor of the current provided by the phase. m% ROPDU.Input[2].Phase[x].PercentLoad Measure Percent load consumed on the phase. It is the ratio :current consumed / the nominal current of the PDU.% ROPDU.Input[2].Phase[x].PhaseID Constant Phase ID identifier depending of the wiring :1 : Line 1 to Neutral2 : Line 2 to Neutral3 : Line 3 to Neutral- ROPDU.Input[2].Phase[x].PowerFactor HideMeasure Ratio of active power / apparent power provided by thephase.Value 0 to 100 for Cos PHI = 0.00 to 1.00m% ROTable 8. ePDU CLI Objects (Continued)XML Object Name Type Description Unit Access