LCD Interface OperationEaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 47Alarms History MenuThe Alarms History menu allows you to scroll through the last 50 logged alarms, beginning with the most recentalarm. The Alarms History screens contain the type of alarm, the date (MM/DD/YYYY), and time (hh:mm:ss)when the alarm occurred (see Figure 45).On the Main Menu, scroll up or down to highlight Alarms History. Press ENTER to display the most recentalarm in the history log. Scroll up or down to view the alarms. When you finish your review, press ESC to returnto the previous menu.ESCEnter Down DownTemperature highwarning07/07/201101:05:44Alarms HistoryAlarms HistoryInput frequencyout of range09/05/201114:23:32Alarms HistoryInput current highwarning09/05/201114:23:32Alarms HistoryMeterSettingsControlePDU InfoActive AlarmsMain MenuAlarms HistoryFigure 45. Example Alarm History DisplaysMeter MenuThe Meter menu provides measurement data for the following submenus:l ePDUl Sections (not available for sections that do not have current measurement)l Outlets (not available for MI and SW ePDUs)l Environment (only available if an EMP is installed)On the Main Menu, scroll up or down to highlight Meter. Press ENTER. Scroll up or down to select a submenuand press ENTER to display the submenu options. Press ESC to return to the previous menu.Alarms HistoryMeterSettingsControlePDU InfoActive AlarmsMain MenuESCEnterePDUEnvironmentMeterSectionsOutletsMeterFigure 46. Example Meter Menu DisplayNOTE The measurement data for each screen is refreshed every two seconds.ePDU SubmenuThese screens display Total Input data measurements for ePDUs. In addition to Total Input measurements, youcan view Phase Input data measurements for 3Ph, split-phase, and dual input ePDUs. Depending on the ePDUelectrical topology, different ePDU measures will display in the Total Input and the Input Phase meter screens.