NOTE For FTP operation, FTP must be enabled (default setting) in the Web pages(Network > Security > Global > FTP enable).Maintenance and AlarmsEaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 12918. Open a DOS command window on a computer that is also connected to network.19. Change directory (CD) to the location of the XML file.20. Open an FTP session using the following command:>ftp where = the IP address displayed on LCD21. Type the default login and password (“admin” and “admin”).22. At the command prompt, type the following command:>cd config/hw>dir23. If an XML file already exists, type the following command to delete the XML file:>delete 24. To upload the configuration file to the eNMC module, type the following command:>put where <config file> = the file name to be downloaded to the eNMC moduleNOTE Keep the name exactly as it is downloaded from the website. Inparticular, it must begin with the prefix “epdu_cfg_” or the eNMC module will notrecognize it.25. Type the following command and ensure that the new file exists:>dir26. Type the following command to quit the FTP session:>quit27. Go to “Reboot the eNMC Module and Reset the ePDU” on page 130.28. Connect the USB device with the uploaded hardware configurtion file to the ePDU that has just has theeNMC.29. Using the LCD display, follow the procedure to “Load the eNMC Configuration File from the USB” onpage 54.30. Go to “Reboot the eNMC Module and Reset the ePDU” on page 130.NOTE To perform the eNMC configuration upload with USB, only one hardwareconfiguration file must be stored in the USB key.