Serial Interface OperationEaton ePDU G3 Operation Manual P-164000277—Rev 1 www.eaton.com/ePDU 75PDU.Gang[x].Pole[1].ReactivePower HideMeasure Reactive Power provided by the pole. dVARROPDU.Gang[x].Pole[1].Statistic[4].Energy HideMeasure Energy counter since last reset. As it is reset to 0, therelated timestamp is updated with the current RTC value.Wh ROPDU.Gang[x].Pole[1].Statistic[5].Energy HideMeasure Energy counter since last reset. When it is reset to 0 thenat the same time the related timestamp is updated withthe current RTC value.Wh ROPDU.Gang[x].Pole[1].Voltage HideMeasure Voltage Measured on the pole. cV ROPDU.Gang[x].Pole[2].ActivePower HideMeasure Active Power provided by the pole. dW ROPDU.Gang[x].Pole[2].ApparentPower HideMeasure Apparent Power provided by the pole. dVA ROPDU.Gang[x].Pole[2].Current HideMeasure Current Power provided by the pole. mA ROPDU.Gang[x].Pole[2].PeakFactor HideMeasure Crest factor of the current provided by the pole. m% ROPDU.Gang[x].Pole[2].PhaseID Constant Phase number that is connected to the pole: 1, 2, or 3. - ROPDU.Gang[x].Pole[2].PowerFactor HideMeasure Ratio of active power / apparent power provided by thepole of the breaker or outlet section.m% ROPDU.Gang[x].Pole[2].ReactivePower HideMeasure Reactive Power provided by the pole. dVARROPDU.Gang[x].Pole[2].Statistic[4].Energy HideMeasure Energy counter since last reset. As it is reset to 0, therelated timestamp is updated with the current RTC value.Wh ROPDU.Gang[x].Pole[2].Voltage HideMeasure Voltage Measured on the pole. cV ROPDU.Gang[x].PowerFactor Measure Ratio of active power / apparent power provided by thebreaker or outlet section.m% ROPDU.Gang[x].PresentStatus.OverCurrent AlarmL1 0: No threshold triggered1: Warning low threshold triggered2: Critical low threshold triggered3: Warning high threshold triggered4: Critical high threshold triggered- ROPDU.Gang[x].PresentStatus.OverVoltage AlarmL1 0: No threshold triggered1: Warning low threshold triggered2: Critical low threshold triggered3: Warning high threshold triggered4: Critical high threshold triggered- ROPDU.Gang[x].PresentStatus.SwitchOnOff AlarmL1 - ROPDU.Gang[x].PresentStatus.Tripped AlarmL1 0 : Breaker closed1 : Breaker tripped (or open)- ROPDU.Gang[x].ReactivePower Measure Reactive Power provided by the breaker/section. For adouble pole breaker, the reactive power for the two polesis combined.dVARROPDU.Gang[x].Statistic[3].Current Measure Current peak consumption since last reset.As it is reset to 0, the related timestamp is updated withthe current RTC value.When a value higher than the stored value is detected, thestored valued is overwritten.mA ROTable 8. ePDU CLI Objects (Continued)XML Object Name Type Description Unit Access