3-94 UR FAMILY – COMMUNICATIONS GUIDEMODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION33.5.2.58 Phase instantaneous overcurrent (PhsIoc)This element is instantiated in the following products: B30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60, N60,T35, T60.Table 3-103: Phase instantaneous overcurrent data objectsDpoPhsφ SPS PHS DIST Z# DPO θ operand in Phase-To-PhaseRstVal BOOLEAN ST PHS DIST Z# DPO θ ROpPhsφ SPS PH DIST Z # OP θ operand RstVal BOOLEAN ST PH DIST Z# OP θ RASupnφ SPS PHS DIST Z# SUPN θ operand in Phase-To-PhaseRstVal BOOLEAN ST PHS DIST Z# SUPN θ RBlkRefγ ORG PHS DIST Z# BLK setting for setting groupγ.RsetSrcRef ObjectReference SP PHS DIST Z# BLK. reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRefγ2 ORG instantiated only in logical node instance1RsetSrcRef ObjectReference SP setting FORCE SELF-POLAR reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CInRefγ3 ORG instantiated only in logical node instance1RsetSrcRef ObjectReference SP setting FORCE MEM-POLAR l reference to the data attribute to input R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CLNName: PhsIocPIOC# LDevice inst: Prot UR element: Phase Instantaneous Overcurrent element #data obj. data attribute Type FC UR Name Description R/W/CStr ACD PHASE IOC# PKP operands (includingindividual three phases), which indicatesOp will operate when delay expiresRgeneral BOOLEAN ST PHASE IOC# PKP RdirGeneral ENUMERATED ST 0, the code for unknown RphsA BOOLEAN ST PHASE IOC# PKP A RdirPhsA ENUMERATED ST 0, the code for unknown RphsB BOOLEAN ST PHASE IOC# PKP B RdirPhsB ENUMERATED ST 0, the code for unknown RphsC BOOLEAN ST PHASE IOC# PKP C RdirPhsC ENUMERATED ST 0, the code for unknown ROp ACT PHASE IOC# OP operands (includingindividual three phases)Rgeneral BOOLEAN ST PHASE IOC# OP RphsA BOOLEAN ST PHASE IOC# OP A RphsB BOOLEAN ST PHASE IOC# OP B RphsC BOOLEAN ST PHASE IOC# OP C RDpo SPS PHASE IOC# DPO operand RstVal BOOLEAN ST PHASE IOC# DPO RDpoPhsβ SPS PHASE IOC# DPO β operands” (where βrefers to Phase-A, B or C)RstVal BOOLEAN ST PHASE IOC# DPO β (where βrefers to Phase-A, B or C)RBlkRefγβ ORG PHASE IOC# BLOCK β setting for settinggroup γ.” (where β refers to Phase-A, B orC)RsetSrcRef ObjectReference SP PHASE IOC# BLOCK β (where βrefers to Phase-A, B or C)reference to the data attribute to input R/CLNName: PhsDisPDIS# LDevice inst: Prot UR element: Phase Distance Z# settingsdata obj. data attribute Type FC UR Name Description R/W/C