3-166 UR FAMILY – COMMUNICATIONS GUIDEMODEL IMPLEMENTATION CONFORMANCE STATEMENT (MICS) CHAPTER 3: IEC 61850 COMMUNICATION33.5.4.8 Field contact inputs (FCIn)This element is instantiated in all UR products (B30, B90, C30, C60, C70, D30, D60, F35, F60, G30, G60, L30, L60, L90, M60,N60, T35, T60).Table 3-181: Field contact input data objectsctlModel CtlModels CF 0 RBlkOpn SPC Disconnect switch open commandsblocked from all sources includingprotectionRstVal BOOLEAN ST Disc0XSWI#.BlkOpn.stVal RctlModel CtlModels CF 0 RBlkCls SPC Disconnect switch close commandsblocked from all sourcesRstVal BOOLEAN ST Disc0XSWI#.BlkCls.stVal RctlModel CtlModels CF 0 RInRef1 ORG SWITCH # φA/3P CLSD setting” if Θ=”1”,“SWITCH # φB CLSD setting” if Θ=”2”, or“SWITCH # φC CLSD setting” if Θ=”3RGEORG RsetSrcRef ObjectReference SP SWITCH # φA/3P CLSD if Θ=”1”,SWITCH # φB CLSD if Θ=”2”, orSWITCH # φC CLSD if Θ=”3”reference to the data attribute to input R/CVISIBLESTRING255SP R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CVISIBLESTRING255SP If reference is external to thisIED, mapped to the source’sGOOSE control block, else emptystringR/CcdcNs VISIBLESTRING255EX Name of the GE Multilinnamespace at the time of thisfirmware releaseRcdcName VISIBLESTRING255EX GEORG RInRef2 ORG SWITCH # φA/3P OPND setting” if Θ=”1”,“SWITCH # φB OPND setting” if Θ=”2”, or“SWITCH # φC OPND setting” if Θ=”3RGEORG RsetSrcRef ObjectReference SP SWITCH # φA/3P OPND if Θ=”1”,SWITCH # φB OPND if Θ=”2”, orSWITCH # φC OPND if Θ=”3”reference to the data attribute to input R/CVISIBLESTRING255SP R/CsetSrcCB ObjectReference SP source GoCB of input if via GOOSE R/CVISIBLESTRING255SP If reference is external to thisIED, mapped to the source’sGOOSE control block, else emptystringR/CcdcNs VISIBLESTRING255EX Name of the GE Multilinnamespace at the time of thisfirmware releaseRcdcName VISIBLESTRING255EX GEORG RLNName: FCInGGIO1 LDevice inst: System UR element: Field Contact Inputsdata obj. data attribute Type FC UR Name Description R/W/CIndΘ SPS FCI Θ On operand value RstVal BOOLEAN ST FCI Θ On RLNName: DiscΘXSWI# LDevice inst: System UR element: Disconnect Control element #data obj. data attribute Type FC UR Name Description R/W/C