5-166 D30 Line Distance Relay GE Multilin5.6 CONTROL ELEMENTS 5 SETTINGS5EXAMPLE 2: BREAKER TRIP CIRCUIT INTEGRITY MONITORINGIf it is required to monitor the trip circuit continuously, independent of the breaker position (open or closed), a method tomaintain the monitoring current flow through the trip circuit when the breaker is open must be provided (as shown in the fig-ure below). This can be achieved by connecting a suitable resistor (see figure below) across the auxiliary contact in the tripcircuit. In this case, it is not required to supervise the monitoring circuit with the breaker position – the BLOCK setting isselected to “Off”. In this case, the settings are as follows (EnerVista UR Setup example shown).Figure 5–95: TRIP CIRCUIT EXAMPLE 2TripCoil52aVIH1aH1cH1bUR Relay - Form-AV = Voltage MonitorI = Current MonitorDC+DC–827074A2.VSDR By-passResistorTable 5–19: VALUES OF RESISTOR ‘R’POWERSUPPLY (V DC)RESISTANCE(OHMS)POWER(WATTS)24 1000 230 5000 248 10000 2110 25000 5125 25000 5250 50000 5