GE Multilin D30 Line Distance Relay B-29APPENDIX B B.4 MEMORY MAPPINGB71FA Line Pickup Block 0 to 65535 --- 1 F300 071FB Line Pickup Target 0 to 2 --- 1 F109 0 (Self-reset)71FC Line Pickup Events 0 to 1 --- 1 F102 0 (Disabled)71FD Terminal Open 0 to 65535 --- 1 F300 071FE Autoreclose Accelerate 0 to 65535 --- 1 F300 0Phase Directional Overcurrent (Read/Write Grouped Setting) (2 modules)7260 Phase Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)7261 Phase Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)7262 Phase Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 07263 Phase Directional Overcurrent 1 ECA 0 to 359 --- 1 F001 307264 Phase Directional Overcurrent 1 Pol V Threshold 0 to 3 pu 0.001 F001 7007265 Phase Directional Overcurrent 1 Block Overcurrent 0 to 1 --- 1 F126 0 (No)7266 Phase Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)7267 Phase Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)7268 Reserved (8 items) 0 to 1 --- 1 F001 07270 ...Repeated for Phase Directional Overcurrent 2Neutral Directional Overcurrent (Read/Write Grouped Setting) (2 modules)7280 Neutral Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)7281 Neutral Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)7282 Neutral Directional Overcurrent 1 Polarizing 0 to 2 --- 1 F230 0 (Voltage)7283 Neutral Directional Overcurrent 1 Forward ECA -90 to 90 ° Lag 1 F002 757284 Neutral Directional Overcurrent 1 Forward Limit Angle 40 to 90 degrees 1 F001 907285 Neutral Directional Overcurrent 1 Forward Pickup 0.002 to 30 pu 0.001 F001 507286 Neutral Directional Overcurrent 1 Reverse Limit Angle 40 to 90 degrees 1 F001 907287 Neutral Directional Overcurrent 1 Reverse Pickup 0.002 to 30 pu 0.001 F001 507288 Neutral Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)7289 Neutral Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 0728A Neutral Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)728B Neutral Directional Overcurrent 1 Polarizing Voltage 0 to 1 --- 1 F231 0 (Calculated V0)728C Neutral Directional Overcurrent 1 Op Current 0 to 1 --- 1 F196 0 (Calculated 3I0)728D Neutral Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 0728E Neutral Directional Overcurrent 1 Pos Seq Restraint 0 to 0.5 --- 0.001 F001 63728F Reserved 0 to 1 --- 1 F001 07290 ...Repeated for Neutral Directional Overcurrent 2Negative Sequence Directional Overcurrent (Read/Write Grouped Setting) (2 modules)72A0 Negative Sequence Directional Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)72A1 Negative Sequence Directional Overcurrent 1 Source 0 to 5 --- 1 F167 0 (SRC 1)72A2 Negative Sequence Directional Overcurrent 1 Type 0 to 1 --- 1 F179 0 (Neg Sequence)72A3 Neg Sequence Directional Overcurrent 1 Forward ECA 0 to 90 ° Lag 1 F002 7572A4 Neg Seq Directional Overcurrent 1 Forward Limit Angle 40 to 90 degrees 1 F001 9072A5 Neg Sequence Directional Overcurrent 1 Forward Pickup 0.05 to 30 pu 0.01 F001 572A6 Neg Seq Directional Overcurrent 1 Reverse Limit Angle 40 to 90 degrees 1 F001 9072A7 Neg Sequence Directional Overcurrent 1 Reverse Pickup 0.05 to 30 pu 0.01 F001 572A8 Negative Sequence Directional Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)72A9 Negative Sequence Directional Overcurrent 1 Block 0 to 65535 --- 1 F300 072AA Negative Sequence Directional Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)72AB Negative Sequence Directional Overcurrent 1 Offset 0 to 250 ohms 0.01 F001 072AC Neg Seq Directional Overcurrent 1 Pos Seq Restraint 0 to 0.5 --- 0.001 F001 6372AD Reserved (3 items) 0 to 1 --- 1 F001 072B0 ...Repeated for Neg Seq Directional Overcurrent 2Breaker Arcing Current Settings (Read/Write Setting) (2 modules)72C0 Breaker 1 Arcing Current Function 0 to 1 --- 1 F102 0 (Disabled)72C1 Breaker 1 Arcing Current Source 0 to 5 --- 1 F167 0 (SRC 1)72C2 Breaker 1 Arcing Current Initiate A 0 to 65535 --- 1 F300 0Table B–9: MODBUS MEMORY MAP (Sheet 22 of 46)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT