5-36 D30 Line Distance Protection System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5The table shows which of DNP 3.0, IEC 60870-5-104, IEC 60870-5-103, and IEC 61850 protocols are operational on theRS232, RS485, and Ethernet ports. It shows all possible combinations of the PROTOCOL and DNP CHANNEL 1(2) PORT set-tings.j) DNP PROTOCOLPATH: SETTINGS PRODUCT SETUP COMMUNICATIONS DNP PROTOCOLTable 5–6: PORT AND PROTOCOL COMBINATIONSPROTOCOLSETTINGDNP CHANNEL 1(2) PORTSETTINGSRS232 RS485 ETHERNETDNP Channel 1: Eth TCPChannel 2: Eth TCPModbus Modbus DNP, Modbus, IEC 61850Channel 1: Eth TCPChannel 2: noneModbus Modbus DNP, Modbus, IEC 61850Channel 1: noneChannel 2: Eth TCPModbus Modbus DNP, Modbus, IEC 61850Channel 1: Eth UDPChannel 2: noneModbus Modbus DNP, Modbus, IEC 61850Channel 1: Eth TCPChannel 2: RS485Modbus DNP DNP, Modbus, IEC 61850Channel 1: Eth TCPChannel 2: RS232DNP Modbus DNP, Modbus, IEC 61850Channel 1: Eth UDPChannel 2: RS485Modbus DNP DNP, Modbus, IEC 61850Channel 1: Eth UDPChannel 2: RS232DNP Modbus DNP, Modbus, IEC 61850Channel 1: RS485Channel 2: Eth TCPModbus DNP DNP, Modbus, IEC 61850Channel 1: RS232Channel 2: Eth TCPDNP Modbus DNP, Modbus, IEC 61850Channel 1: RS485Channel 2: RS232DNP DNP Modbus, IEC 61850Channel 1: RS232Channel 2: RS485DNP DNP Modbus, IEC 61850Channel 1: RS485Channel 2: noneModbus DNP Modbus, IEC 61850IEC 104 Modbus Modbus IEC 104, Modbus, IEC 61850IEC 103 Modbus IEC 103 Modbus, IEC 61850 DNP PROTOCOL DNP CHANNELSRange: see sub-menu belowMESSAGE DNP ADDRESS:1Range: 0 to 65519 in steps of 1MESSAGE DNP NETWORK CLIENT ADDRESSESRange: see sub-menu belowMESSAGE DNP TCP/UDP PORTNUMBER: 20000Range: 0 to 65535 in steps of 1MESSAGE DNP UNSOL RESPONSEFUNCTION: DisabledRange: Enabled, DisabledMESSAGE DNP UNSOL RESPONSETIMEOUT: 5 sRange: 0 to 60 s in steps of 1MESSAGE DNP UNSOL RESPONSEMAX RETRIES: 10Range: 1 to 255 in steps of 1MESSAGE DNP UNSOL RESPONSEDEST ADDRESS: 1Range: 0 to 65519 in steps of 1