B-56 D30 Line Distance Protection System GE MultilinB.4 MEMORY MAPPING APPENDIX BBIEC 61850 XSWI Configuration (Read/Write Command) (24 modules)B372 Command to Clear XSWI OpCnt (Operation Counter) 0 to 1 --- 1 F126 0 (No)IEC 61850 GGIO1 Configuration Settings (Read/Write Setting)B400 Number of Status Indications in GGIO1 8 to 128 --- 8 F001 8B402 IEC 61850 GGIO1 Indication FlexLogic operands (128items)0 to 4294967295 --- 1 F300 0IEC 61850 Configurable GOOSE Transmission (Read/Write Setting) (8 modules)B5A0 IEC 61850 Configurable GOOSE Function (GoEna) 0 to 1 --- 1 F102 1 (Enabled)B5A1 IEC 61850 Configurable GOOSE ID --- --- --- F209 “GOOSEOut_x_”B5C2 Configurable GOOSE Destination MAC Address --- --- --- F072 0B5C5 IEC 61850 Configurable GOOSE VLAN Transmit Priority 0 to 7 --- 1 F001 4B5C6 IEC 61850 Configurable GOOSE VLAN ID 0 to 4095 --- 1 F001 0B5C7 IEC 61850 Configurable GOOSE ETYPE APPID 0 to 16383 --- 1 F001 0B5C8 IEC 61850 Configurable GOOSE ConfRev (ConfigurationRevision)1 to 4294967295 --- 1 F003 1B5CA IEC 61850 Configurable GOOSE Retransmission Curve 0 to 3 --- 1 F611 3 (Relaxed)B5CB Configurable GOOSE Dataset Items for Transmission(64 items) 0 to 1008 --- 1 F616 0 (None)B60B ...Repeated for module number 2B676 ...Repeated for module number 3B6E1 ...Repeated for module number 4B74C ...Repeated for module number 5B7B7 ...Repeated for module number 6B822 ...Repeated for module number 7B88D ...Repeated for module number 8IEC 61850 Configurable GOOSE Reception (Read/Write Setting) (16 modules)B900 Configurable GOOSE Dataset Items for Reception(32 items)0 to 197 --- 1 F233 0 (None)B920 ...Repeated for module number 2B940 ...Repeated for module number 3B960 ...Repeated for module number 4B980 ...Repeated for module number 5B9A0 ...Repeated for module number 6B9C0 ...Repeated for module number 7B9E0 ...Repeated for module number 8BA00 ...Repeated for module number 9BA20 ...Repeated for module number 10BA40 ...Repeated for module number 11BA60 ...Repeated for module number 12BA80 ...Repeated for module number 13BAA0 ...Repeated for module number 14BAC0 ...Repeated for module number 15BAE0 ...Repeated for module number 16Contact Inputs (Read/Write Setting) (96 modules)BB00 Contact Input 1 Name --- --- --- F205 “Cont Ip 1“BB06 Contact Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)BB07 Contact Input 1 Debounce Time 0 to 16 ms 0.5 F001 20BB08 ...Repeated for Contact Input 2BB10 ...Repeated for Contact Input 3BB18 ...Repeated for Contact Input 4BB20 ...Repeated for Contact Input 5BB28 ...Repeated for Contact Input 6BB30 ...Repeated for Contact Input 7BB38 ...Repeated for Contact Input 8BB40 ...Repeated for Contact Input 9Table B–10: MODBUS MEMORY MAP (Sheet 48 of 62)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT