GE Multilin D30 Line Distance Protection System C-21APPENDIX C C.5 IEC 61850 IMPLEMENTATION VIA ENERVISTA UR SETUPCThe IED Section node describes the configuration of an IED.Figure C–9: SCD FILE STRUCTURE, IED NODEC.5.6 IMPORTING AN SCD FILE WITH ENERVISTA UR SETUPThe following procedure describes how to update the D30 with the new configuration from an SCD file with the EnerVistaUR Setup software.1. Right-click anywhere in the files panel and select the Import Contents From SCD File item.2. Select the saved SCD file and click Open.842794A1.CDRIED Section (IED 1)AccessPoint (name)ServerAuthentication (none)LDevice (inst)LN0 (InType, InClass, inst)DataSet elementsDOI elementsInputsGSEControl elementsReportControl elementsExtRef (iedName, ldInst, prefix, lnClass, lnInst, doName, daName, intAddr)Other ExtRef elements