GE Multilin F60 Feeder Management Relay 5-895 SETTINGS 5.5 GROUPED ELEMENTS5d) PHASE INSTANTANEOUS OVERCURRENT (ANSI 50P)PATH: SETTINGS ÖØ GROUPED ELEMENTS Ö SETTING GROUP 1(6) Ö PHASE CURRENT Ö PHASE IOC 1The phase instantaneous overcurrent element may be used as an instantaneous element with no intentional delay or as aDefinite Time element. The input current is the fundamental phasor magnitude.Figure 5–43: PHASE IOC1 SCHEME LOGIC PHASE IOC1PHASE IOC1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE PHASE IOC1 SIGNALSOURCE: SRC 1Range: SRC 1, SRC 2MESSAGE PHASE IOC1PICKUP: 1.000 puRange: 0.000 to 30.000 pu in steps of 0.001MESSAGE PHASE IOC1 PICKUPDELAY: 0.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PHASE IOC1 RESETDELAY: 0.00 sRange: 0.00 to 600.00 s in steps of 0.01MESSAGE PHASE IOC1 BLOCK A:OffRange: FlexLogic™ operandMESSAGE PHASE IOC1 BLOCK B:OffRange: FlexLogic™ operandMESSAGE PHASE IOC1 BLOCK C:OffRange: FlexLogic™ operandMESSAGE PHASE IOC1TARGET: Self-resetRange: Self-reset, Latched, DisabledMESSAGE PHASE IOC1EVENTS: DisabledRange: Disabled, EnabledIA ≥ PICKUPSETTINGPHASE IOC1FUNCTION:Enabled = 1Disabled = 0SETTINGPHASE IOC1SOURCE:IAIBICPHASE IOC1BLOCK-A:Off = 0SETTINGSETTINGIB ≥ PICKUPRUNPHASE IOC1PICKUP:RUNIC ≥ PICKUPRUNPHASE IOC1PICKUPDELAY:SETTINGSPHASE IOC1 RESETDELAY:tPKPtRSTtPKPtRSTtPKPtRST827033A6.VSDFLEXLOGICOPERANDSPHASE IOC1 B PKPPHASE IOC1 B DPOPHASE IOC1 PKPPHASE IOC1 C PKPPHASE IOC1 C DPOPHASE IOC1 A OPPHASE IOC1 B OPPHASE IOC1 OPORANDORANDANDPHASE IOC1 A DPOPHASE IOC1 A PKPPHASE IOC1 C OPPHASE IOC1BLOCK-B:Off = 0SETTINGPHASE IOC1BLOCK-C:Off = 0SETTINGPHASE IOC1 DPOAND