B-28 F60 Feeder Management Relay GE MultilinB.4 MEMORY MAPPING APPENDIX BBNegative Sequence Time Overcurrent (Read/Write Grouped Setting) (2 modules)6300 Negative Sequence Time Overcurrent 1 Function 0 to 1 --- 1 F102 0 (Disabled)6301 Negative Sequence Time Overcurrent 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)6302 Negative Sequence Time Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 10006303 Negative Sequence Time Overcurrent 1 Curve 0 to 16 --- 1 F103 0 (IEEE Mod Inv)6304 Negative Sequence Time Overcurrent 1 Multiplier 0 to 600 --- 0.01 F001 1006305 Negative Sequence Time Overcurrent 1 Reset 0 to 1 --- 1 F104 0 (Instantaneous)6306 Negative Sequence Time Overcurrent 1 Block 0 to 65535 --- 1 F300 06307 Negative Sequence Time Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)6308 Negative Sequence Time Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)6309 Reserved (7 items) 0 to 1 --- 1 F001 06310 ...Repeated for Negative Sequence Time Overcurrent 2Negative Sequence Instantaneous Overcurrent (Read/Write Grouped Setting) (2 modules)6400 Negative Sequence Instantaneous OC 1 Function 0 to 1 --- 1 F102 0 (Disabled)6401 Negative Sequence Instantaneous OC 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)6402 Negative Sequence Instantaneous Overcurrent 1 Pickup 0 to 30 pu 0.001 F001 10006403 Negative Sequence Instantaneous Overcurrent 1 Delay 0 to 600 s 0.01 F001 06404 Negative Sequence Instantaneous OC 1 Reset Delay 0 to 600 s 0.01 F001 06405 Negative Sequence Instantaneous Overcurrent 1 Block 0 to 65535 --- 1 F300 06406 Negative Sequence Instantaneous Overcurrent 1 Target 0 to 2 --- 1 F109 0 (Self-reset)6407 Negative Sequence Instantaneous Overcurrent 1 Events 0 to 1 --- 1 F102 0 (Disabled)6408 Reserved (8 items) 0 to 1 --- 1 F001 06410 ...Repeated for Negative Sequence Instantaneous OC 2Negative Sequence Overvoltage (Read/Write Grouped Setting)64A0 Negative Sequence Overvoltage Function 0 to 1 --- 1 F102 0 (Disabled)64A1 Negative Sequence Overvoltage Source 0 to 5 --- 1 F167 0 (SRC 1)64A2 Negative Sequence Overvoltage Pickup 0 to 1.25 pu 0.001 F001 30064A3 Negative Sequence Overvoltage Pickup Delay 0 to 600 s 0.01 F001 5064A4 Negative Sequence Overvoltage Reset Delay 0 to 600 s 0.01 F001 5064A5 Negative Sequence Overvoltage Block 0 to 65535 --- 1 F300 064A6 Negative Sequence Overvoltage Target 0 to 2 --- 1 F109 0 (Self-reset)64A7 Negative Sequence Overvoltage Events 0 to 1 --- 1 F102 0 (Disabled)Overfrequency (Read/Write Setting) (4 modules)64D0 Overfrequency 1 Function 0 to 1 --- 1 F102 0 (Disabled)64D1 Overfrequency 1 Block 0 to 65535 --- 1 F300 064D2 Overfrequency 1 Source 0 to 5 --- 1 F167 0 (SRC 1)64D3 Overfrequency 1 Pickup 20 to 65 Hz 0.01 F001 605064D4 Overfrequency 1 Pickup Delay 0 to 65.535 s 0.001 F001 50064D5 Overfrequency 1 Reset Delay 0 to 65.535 s 0.001 F001 50064D6 Overfrequency 1 Target 0 to 2 --- 1 F109 0 (Self-reset)64D7 Overfrequency 1 Events 0 to 1 --- 1 F102 0 (Disabled)64D8 Reserved (4 items) 0 to 1 --- 1 F001 064DC ...Repeated for Overfrequency 264E8 ...Repeated for Overfrequency 364F4 ...Repeated for Overfrequency 4Sensitive Directional Power (Read/Write Grouped Setting) (2 modules)66A0 Sensitive Directional Power 1 Function 0 to 1 --- 1 F102 0 (Disabled)66A1 Sensitive Directional Power 1 Signal Source 0 to 5 --- 1 F167 0 (SRC 1)66A2 Sensitive Directional Power 1 RCA 0 to 359 degrees 1 F001 066A3 Sensitive Directional Power 1 Calibration 0 to 0.95 degrees 0.05 F001 066A4 Sensitive Directional Power 1 STG1 SMIN -1.2 to 1.2 pu 0.001 F002 10066A5 Sensitive Directional Power 1 STG1 Delay 0 to 600 s 0.01 F001 5066A6 Sensitive Directional Power 1 STG2 SMIN -1.2 to 1.2 pu 0.001 F002 10066A7 Sensitive Directional Power 1 STG2 Delay 0 to 600 s 0.01 F001 2000Table B–9: MODBUS MEMORY MAP (Sheet 21 of 46)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT