GE Multilin F60 Feeder Management Relay 6-56 ACTUAL VALUES 6.2 STATUS66.2.7 AUTORECLOSEPATH: ACTUAL VALUES Ö STATUS ÖØ AUTORECLOSE Ö AUTORECLOSE 1The automatic reclosure shot count is shown here.6.2.8 REMOTE DEVICESa) STATUSPATH: ACTUAL VALUES Ö STATUS ÖØ REMOTE DEVICES STATUSThe present state of up to 16 programmed Remote Devices is shown here. The ALL REMOTE DEVICES ONLINE message indi-cates whether or not all programmed Remote Devices are online. If the corresponding state is "No", then at least onerequired Remote Device is not online.b) STATISTICSPATH: ACTUAL VALUES Ö STATUS ÖØ REMOTE DEVICES STATISTICS Ö REMOTE DEVICE 1(16)Statistical data (2 types) for up to 16 programmed Remote Devices is shown here.The StNum number is obtained from the indicated Remote Device and is incremented whenever a change of state of atleast one DNA or UserSt bit occurs. The SqNum number is obtained from the indicated Remote Device and is incrementedwhenever a GSSE message is sent. This number will rollover to zero when a count of 4,294,967,295 is incremented. AUTORECLOSE 1AUTORECLOSE 1SHOT COUNT: 0Range: 0, 1, 2, 3, 4 REMOTE DEVICES STATUSAll REMOTE DEVICESONLINE: NoRange: Yes, NoMESSAGE REMOTE DEVICE 1STATUS: OfflineRange: Online, Offline↓MESSAGE REMOTE DEVICE 16STATUS: OfflineRange: Online, Offline REMOTE DEVICE 1REMOTE DEVICE 1StNum: 0MESSAGE REMOTE DEVICE 1SqNum: 0