B-64 F60 Feeder Management Relay GE MultilinB.4 MEMORY MAPPING APPENDIX BBF501UR_UINT16: LED STATUSLow byte of register indicates LED status with bit 0 representingthe top LED and bit 7 the bottom LED. A bit value of 1 indicatesthe LED is on, 0 indicates the LED is off.F502BITFIELD: ELEMENT OPERATE STATESEach bit contains the operate state for an element. See the F124format code for a list of element IDs. The operate bit for element IDX is bit [X mod 16] in register [X/16].F504BITFIELD: 3-PHASE ELEMENT STATEF505BITFIELD: CONTACT OUTPUT STATE0 = Contact State, 1 = Voltage Detected, 2 = Current DetectedF506|BITFIELD: 1 PHASE ELEMENT STATE0 = Pickup, 1 = OperateF507BITFIELD: COUNTER ELEMENT STATE0 = Count Greater Than, 1 = Count Equal To, 2 = Count Less ThanF509BITFIELD: SIMPLE ELEMENT STATE0 = OperateF511BITFIELD: 3-PHASE SIMPLE ELEMENT STATE0 = Operate, 1 = Operate A, 2 = Operate B, 3 = Operate CF512ENUMERATION: HARMONIC NUMBERF515ENUMERATION ELEMENT INPUT MODE0 = Signed, 1 = AbsoluteF516ENUMERATION ELEMENT COMPARE MODE0 = Level, 1 = DeltaF517ENUMERATION: ELEMENT DIRECTION OPERATION0 = Over, 1 = UnderF518ENUMERATION: FLEXELEMENT™ UNITS0 = Milliseconds, 1 = Seconds, 2 = MinutesF519ENUMERATION: NON-VOLATILE LATCH0 = Reset-Dominant, 1 = Set-DominantF522ENUMERATION: TRANSDUCER DCMA OUTPUT RANGE0 = –1 to 1 mA; 1 = 0 to 1 mA; 2 = 4 to 20 mAF523ENUMERATION: DNP OBJECTS 20, 22, AND 23 DEFAULTVARIATIONbitmask element state0 Pickup1 Operate2 Pickup Phase A3 Pickup Phase B4 Pickup Phase C5 Operate Phase A6 Operate Phase B7 Operate Phase Cbitmask harmonic bitmask harmonic0 2ND 12 14TH1 3RD 13 15TH2 4TH 14 16TH3 5TH 15 17TH4 6TH 16 18TH5 7TH 17 19TH6 8TH 18 20TH7 9TH 19 21ST8 10TH 20 22ND9 11TH 21 23RD10 12TH 22 24TH11 13TH 23 25THbitmask Default Variation0 11 22 53 6