GE Multilin F60 Feeder Management Relay 5-1335 SETTINGS 5.6 CONTROL ELEMENTS5APPLICATION EXAMPLEConsider an application where the selector switch is used to control Setting Groups 1 through 4 in the relay. The settinggroups are to be controlled from both User-Programmable Pushbutton 1 and from an external device via Contact Inputs 1through 3. The active setting group shall be available as an encoded 3-bit word to the external device and SCADA via out-put contacts 1 through 3. The pre-selected setting group shall be applied automatically after 5 seconds of inactivity of thecontrol inputs. When the relay powers up, it should synchronize the setting group to the 3-bit control input.Make the following changes to Setting Group Control in the SETTINGS ÖØ CONTROL ELEMENTS Ö SETTING GROUPS menu:SETTING GROUPS FUNCTION: “Enabled” GROUP 4 ACTIVATE ON: “SELECTOR 1 POS 4"SETTING GROUPS BLK: “Off” GROUP 5 ACTIVATE ON: “Off”GROUP 2 ACTIVATE ON: “SELECTOR 1 POS 2" GROUP 6 ACTIVATE ON: “Off”GROUP 3 ACTIVATE ON: “SELECTOR 1 POS 3"Make the following changes to Selector Switch element in the SETTINGS ÖØ CONTROL ELEMENTS ÖØ SELECTOR SWITCH ÖSELECTOR SWITCH 1 menu to assign control to User Programmable Pushbutton 1 and Contact Inputs 1 through 3:SELECTOR 1 FUNCTION: “Enabled” SELECTOR 1 3BIT A0: “CONT IP 1 ON”SELECTOR 1 FULL-RANGE: “4” SELECTOR 1 3BIT A1: “CONT IP 2 ON”SELECTOR 1 STEP-UP MODE: “Time-out” SELECTOR 1 3BIT A2: “CONT IP 3 ON”SELECTOR 1 TIME-OUT: “5.0 s” SELECTOR 1 3BIT MODE: “Time-out”SELECTOR 1 STEP-UP: “PUSHBUTTON 1 ON” SELECTOR 1 3BIT ACK: “Off”SELECTOR 1 ACK: “Off” SELECTOR 1 POWER-UP MODE: “Synchronize”Now, assign the contact output operation (assume the H6E module) to the Selector Switch element by making the followingchanges in the SETTINGS ÖØ INPUTS/OUTPUTS ÖØ CONTACT OUTPUTS menu:OUTPUT H1 OPERATE: “SELECTOR 1 BIT 0"OUTPUT H2 OPERATE: “SELECTOR 1 BIT 1"OUTPUT H3 OPERATE: “SELECTOR 1 BIT 2"Finally, assign configure User-Programmable Pushbutton 1 by making the following changes in the SETTINGS Ö PRODUCTSETUP ÖØ USER-PROGRAMMABLE PUSHBUTTONS Ö USER PUSHBUTTON 1 menu:PUSHBUTTON 1 FUNCTION: “Self-reset”PUSHBUTTON 1 DROP-OUT TIME: “0.10 s”The logic for the selector switch is shown below:Figure 5–75: SELECTOR SWITCH LOGIC842012A1.CDRstep upacknowledge3-bit position outonFLEXLOGIC OPERANDSSELECTOR 1 POS 1SELECTOR 1 POS 2SELECTOR 1 POS 3SELECTOR 1 POS 4SELECTOR 1 POS 5SELECTOR 1 POS 6SELECTOR 1 POS 7SELECTOR 1 STP ALARMSELECTOR 1 BIT ALARMSELECTOR 1 ALARMSELECTOR 1 BIT 0SELECTOR 1 BIT 1SELECTOR 1 BIT 2ORFLEXLOGIC OPERANDSRUNSELECTOR 1 POWER-UP MODE:SETTINGSSELECTOR 1 TIME-OUT:SELECTOR 1 STEP-UP MODE:SELECTOR 1 FULL RANGE:SELECTOR 1 STEP-UP:OffSELECTOR 1 FUNCTION:SETTINGSEnabled = 1SELECTOR 1 ACK:OffSELECTOR 1 3BIT A0:OffSELECTOR 1 3BIT A1:OffSELECTOR 1 3BIT A2:OffSELECTOR 1 3BIT ACK:Off 3-bitacknowledgeSELECTOR 1 POSITIONACTUAL VALUE2134567SELECTOR 1 3BIT MODE:SELECTOR 1 PWR ALARM3-bit control in