GE Multilin F60 Feeder Protection System 5-335 SETTINGS 5.2 PRODUCT SETUP5These settings appear only if the F60 is ordered with an Ethernet switch module (type 2S or 2T).The IP address and Modbus TCP port number for the Ethernet switch module are specified in this menu. These settingsare used in advanced network configurations. Please consult the network administrator before making changes to thesesettings. The client software (EnerVista UR Setup, for example) is the preferred interface to configure these settings.The PORT 1 EVENTS through PORT 6 EVENTS settings allow Ethernet switch module events to be logged in the eventrecorder.5.2.5 MODBUS USER MAPPATH: SETTINGS Ö PRODUCT SETUP ÖØ MODBUS USER MAPThe Modbus user map provides read-only access for up to 256 registers. To obtain a memory map value, enter the desiredaddress in the ADDRESS line (this value must be converted from hex to decimal format). The corresponding value is dis-played in the VALUE line. A value of “0” in subsequent register ADDRESS lines automatically returns values for the previousADDRESS lines incremented by “1”. An address value of “0” in the initial register means “none” and values of “0” will be dis-played for all registers. Different ADDRESS values can be entered as required in any of the register positions. MODBUS USER MAPADDRESS 1: 0VALUE: 0Range: 0 to 65535 in steps of 1MESSAGE ADDRESS 2: 0VALUE: 0Range: 0 to 65535 in steps of 1↓MESSAGE ADDRESS 256: 0VALUE: 0Range: 0 to 65535 in steps of 1