GE Multilin F60 Feeder Protection System 1-91 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE18. Select “Ethernet” from the Interface drop-down list. This will display a number of interface parameters that must beentered for proper Ethernet functionality.Figure 1–5: CONFIGURING ETHERNET COMMUNICATIONS9. Enter the relay IP address specified in the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IPADDRESS) in the “IP Address” field.10. Enter the relay slave address and Modbus port address values from the respective settings in the SETTINGS Ö PROD-UCT SETUP ÖØ COMMUNICATIONS ÖØ MODBUS PROTOCOL menu.11. Click the Read Order Code button to connect to the F60 device and upload the order code. If an communications erroroccurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay settingvalues.12. Click OK when the relay order code has been received. The new device will be added to the Site List window (orOnline window) located in the top left corner of the main EnerVista UR Setup window.The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the F60 section tobegin communications.1.3.4 USING THE QUICK CONNECT FEATUREa) USING QUICK CONNECT VIA THE FRONT PANEL RS232 PORTBefore starting, verify that the serial cable is properly connected from the laptop computer to the front panel RS232 portwith a straight-through 9-pin to 9-pin RS232 cable.1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD oronline from http://www.GEmultilin.com). See the Software Installation section for installation details.2. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.