5-44 F60 Feeder Protection System GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5After applying the settings in application example 1, hold down the pushbutton as long as necessary to test all LEDs. Next,release the pushbutton to automatically start stage 2. Once stage 2 has started, the pushbutton can be released. Whenstage 2 is completed, stage 3 will automatically start. The test may be aborted at any time by pressing the pushbutton.c) TRIP AND ALARM LEDSPATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS ÖØ TRIP & ALARM LEDSThe trip and alarm LEDs are in the first LED column (enhanced faceplate) and on LED panel 1 (standard faceplate). Eachindicator can be programmed to become illuminated when the selected FlexLogic™ operand is in the logic 1 state.d) USER-PROGRAMMABLE LED 1(48)PATH: SETTINGS Ö PRODUCT SETUP ÖØ USER-PROGRAMMABLE LEDS ÖØ USER-PROGRAMMABLE LED 1(48)There are 48 amber LEDs across the relay faceplate LED panels. Each of these indicators can be programmed to illumi-nate when the selected FlexLogic™ operand is in the logic 1 state.For the standard faceplate, the LEDs are located as follows.• LED Panel 2: user-programmable LEDs 1 through 24• LED Panel 3: user programmable LEDs 25 through 48For the enhanced faceplate, the LEDs are located as follows.• LED column 2: user-programmable LEDs 1 through 12• LED column 3: user-programmable LEDs 13 through 24• LED column 4: user-programmable LEDs 25 through 36• LED column 5: user-programmable LEDs 37 through 48Refer to the LED indicators section in chapter 4 for additional information on the location of these indexed LEDs.The user-programmable LED settings select the FlexLogic™ operands that control the LEDs. If the LED 1 TYPE setting is“Self-Reset” (the default setting), the LED illumination will track the state of the selected LED operand. If the LED 1 TYPE set-ting is “Latched”, the LED, once lit, remains so until reset by the faceplate RESET button, from a remote device via a com-munications channel, or from any programmed operand, even if the LED operand state de-asserts. TRIP & ALARM LEDSTRIP LED INPUT:OffRange: FlexLogic™ operandMESSAGE ALARM LED INPUT:OffRange: FlexLogic™ operand USER-PROGRAMMABLE LED 1LED 1 OPERAND:OffRange: FlexLogic™ operandMESSAGE LED 1 TYPE:Self-ResetRange: Self-Reset, Latched