6-26 F60 Feeder Protection System GE Multilin6.4 RECORDS 6 ACTUAL VALUES66.4.5 BREAKER MAINTENANCEPATH: ACTUAL VALUES ÖØ RECORDS ÖØ MAINTENANCE Ö BREAKER 1(2)There is an identical menu for each of the breakers. The BKR 1 ARCING AMP values are in units of kA 2 -cycles. Refer to theCOMMANDS ÖØ CLEAR RECORDS menu for clearing breaker arcing current records. The BREAKER OPERATING TIME isdefined as the slowest operating time of breaker poles that were initiated to open.6.4.6 HI-Z RECORDSPATH: ACTUAL VALUES ÖØ RECORDS ÖØ HIZ RECORDSTwo types of high impedance fault detection element records are stored in non-volatile memory and available from thismenu. If the element is triggered by a high impedance overcurrent condition, then the records are displayed in the RMS 1 toRMS 4 actual values. If the element is triggered by high impedance fault detection arcing algorithm, then the records are dis-played in the HIZ 1 to HIZ 4 actual values. Refer to High impedance fault detection section in chapter 5 for more information. BREAKER 1BKR 1 ARCING AMP φA:0.00 kA2-cycMESSAGE BKR 1 ARCING AMP φB:0.00 kA2-cycMESSAGE BKR 1 ARCING AMP φC:0.00 kA2-cycMESSAGE BKR 1 OPERATING TIMEφA: 0 msMESSAGE BKR 1 OPERATING TIMEφB: 0 msMESSAGE BKR 1 OPERATING TIMEφC: 0 msMESSAGE BKR 1 OPERATINGTIME: 0 ms HIZ RECORDSFORCE TRIGGER:NoMESSAGE HIZ 1:NONE1970/01/01 00:00:00MESSAGE HIZ 2:NONE1970/01/01 00:00:00MESSAGE HIZ 3:NONE1970/01/01 00:00:00MESSAGE HIZ 4:NONE1970/01/01 00:00:00MESSAGE RMS 1:NONE1970/01/01 00:00:00MESSAGE RMS 2:NONE1970/01/01 00:00:00MESSAGE RMS 3:NONE1970/01/01 00:00:00MESSAGE RMS 4:NONE1970/01/01 00:00:00