GE Multilin F60 Feeder Protection System 2-132 PRODUCT DESCRIPTION 2.2 SPECIFICATIONS2RTD INPUTSTypes (3-wire): 100 Ω Platinum, 100 & 120 Ω Nickel, 10Ω CopperSensing current: 5 mARange: –50 to +250°CAccuracy: ±2°CIsolation: 36 V pk-pkIRIG-B INPUTAmplitude modulation: 1 to 10 V pk-pkDC shift: TTLInput impedance: 22 kΩIsolation: 2 kVREMOTE INPUTS (IEC 61850 GSSE/GOOSE)Number of input points: 32, configured from 64 incoming bit pairsNumber of remote devices:16Default states on loss of comms.: On, Off, Latest/Off, Latest/OnDIRECT INPUTSNumber of input points: 32No. of remote devices: 16Default states on loss of comms.: On, Off, Latest/Off, Latest/OnRing configuration: Yes, NoData rate: 64 or 128 kbpsCRC: 32-bitCRC alarm:Responding to: Rate of messages failing the CRCMonitoring message count: 10 to 10000 in steps of 1Alarm threshold: 1 to 1000 in steps of 1Unreturned message alarm:Responding to: Rate of unreturned messages in the ringconfigurationMonitoring message count: 10 to 10000 in steps of 1Alarm threshold: 1 to 1000 in steps of 1TELEPROTECTIONNumber of input points: 16No. of remote devices: 3Default states on loss of comms.: On, Off, Latest/Off, Latest/OnRing configuration: NoData rate: 64 or 128 kbpsCRC: 32-bit2.2.6 POWER SUPPLYLOW RANGENominal DC voltage: 24 to 48 VMin/max DC voltage: 20 / 60 VVoltage loss hold-up: 20 ms duration at nominalNOTE: Low range is DC only.HIGH RANGENominal DC voltage: 125 to 250 VMin/max DC voltage: 88 / 300 VNominal AC voltage: 100 to 240 V at 50/60 HzMin/max AC voltage: 88 / 265 V at 25 to 100 HzVoltage loss hold-up: 200 ms duration at nominalALL RANGESVolt withstand: 2 × Highest Nominal Voltage for 10 msPower consumption: typical = 15 to 20 W/VAmaximum = 50 W/VAcontact factory for exact order code con-sumptionINTERNAL FUSERATINGSLow range power supply: 8 A / 250 VHigh range power supply: 4 A / 250 VINTERRUPTING CAPACITYAC: 100 000 A RMS symmetricalDC: 10 000 A2.2.7 OUTPUTSFORM-A RELAYMake and carry for 0.2 s: 30 A as per ANSI C37.90Carry continuous: 6 ABreak (DC inductive, L/R = 40 ms):Operate time: < 4 msContact material: silver alloyLATCHING RELAYMake and carry for 0.2 s: 30 A as per ANSI C37.90Carry continuous: 6 ABreak at L/R of 40 ms: 0.25 A DC max.Operate time: < 4 msContact material: silver alloyControl: separate operate and reset inputsControl mode: operate-dominant or reset-dominantFORM-A VOLTAGE MONITORApplicable voltage: approx. 15 to 250 V DCTrickle current: approx. 1 to 2.5 mAFORM-A CURRENT MONITORThreshold current: approx. 80 to 100 mAVOLTAGE CURRENT24 V 1 A48 V 0.5 A125 V 0.3 A250 V 0.2 A