GE Multilin L60 Line Phase Comparison System 5-715 SETTINGS 5.2 PRODUCT SETUP5See the figure in the Setting Groups section of the Control Elements section later in this chapter for an example of groupactivation.5.2.11 USER-PROGRAMMABLE SELF TESTSFor user-programmable self-tests for CyberSentry, use the Setup > Security > Supervisory menu instead.PATH: SETTINGS PRODUCT SETUP USER-PROGRAMMABLE SELF TESTSAll major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets. Mostof the minor alarms can be disabled if desired.When in the “Disabled” mode, minor alarms will not assert a FlexLogic operand, write to the event recorder, or display tar-get messages. Moreover, they will not trigger the ANY MINOR ALARM or ANY SELF-TEST messages. When in the “Enabled”mode, minor alarms continue to function along with other major and minor alarms. Refer to the Relay self-tests section inchapter 7 for additional information on major and minor self-test alarms.5.2.12 CONTROL PUSHBUTTONSPATH: SETTINGS PRODUCT SETUP CONTROL PUSHBUTTONS CONTROL PUSHBUTTON 1(7)There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced frontpanels. These are user-programmable and can be used for various applications such as performing an LED test, switchingsetting groups, and invoking and scrolling though user-programmable displays. USER-PROGRAMMABLE SELF TESTSDIRECT RING BREAKFUNCTION: EnabledRange: Disabled, Enabled. Valid for units equipped withDirect Input/Output module.MESSAGE DIRECT DEVICE OFFFUNCTION: EnabledRange: Disabled, Enabled. Valid for units equipped withDirect Input/Output module.MESSAGE REMOTE DEVICE OFFFUNCTION: EnabledRange: Disabled, Enabled.MESSAGE FIRST ETHERNET FAILFUNCTION: DisabledRange: Disabled, Enabled.MESSAGE SEC. ETHERNET FAILFUNCTION: DisabledRange: Disabled, Enabled.MESSAGE THIRD ETHERNET FAILFUNCTION: DisabledRange: Disabled, Enabled.MESSAGE BATTERY FAILFUNCTION: EnabledRange: Disabled, Enabled.MESSAGE SNTP FAILFUNCTION: EnabledRange: Disabled, Enabled.MESSAGE IRIG-B FAILFUNCTION: EnabledRange: Disabled, Enabled.MESSAGE PTP FAILFUNCTION: EnabledRange: Disabled, Enabled.MESSAGE SFP MODULE FAILFUNCTION: DisabledRange: Disabled, Enabled. CONTROL PUSHBUTTON 1CONTROL PUSHBUTTON 1FUNCTION: DisabledRange: Disabled, EnabledMESSAGE CONTROL PUSHBUTTON 1EVENTS: DisabledRange: Disabled, Enabled