GE Multilin L60 Line Phase Comparison System B-15APPENDIX B B.4 MEMORY MAPPINGB2348 Fault 1 Prefault Phase C Current Angle -359.9 to 0 degrees 0.1 F002 02349 Fault 1 Prefault Phase A Voltage Magnitude 0 to 999999.999 V 0.001 F060 0234B Fault 1 Prefault Phase A Voltage Angle -359.9 to 0 degrees 0.1 F002 0234C Fault 1 Prefault Phase B Voltage Magnitude 0 to 999999.999 V 0.001 F060 0234E Fault 1 Prefault Phase B Voltage Angle -359.9 to 0 degrees 0.1 F002 0234F Fault 1 Prefault Phase C Voltage Magnitude 0 to 999999.999 V 0.001 F060 02351 Fault 1 Prefault Phase C Voltage Angle -359.9 to 0 degrees 0.1 F002 02352 Fault 1 Phase A Current Magnitude 0 to 999999.999 A 0.001 F060 02354 Fault 1 Phase A Current Angle -359.9 to 0 degrees 0.1 F002 02355 Fault 1 Phase B Current Magnitude 0 to 999999.999 A 0.001 F060 02357 Fault 1 Phase B Current Angle -359.9 to 0 degrees 0.1 F002 02358 Fault 1 Phase C Current Magnitude 0 to 999999.999 A 0.001 F060 0235A Fault 1 Phase C Current Angle -359.9 to 0 degrees 0.1 F002 0235B Fault 1 Phase A Voltage Magnitude 0 to 999999.999 V 0.001 F060 0235D Fault 1 Phase A Voltage Angle -359.9 to 0 degrees 0.1 F002 0235E Fault 1 Phase B Voltage Magnitude 0 to 999999.999 V 0.001 F060 02360 Fault 1 Phase B Voltage Angle -359.9 to 0 degrees 0.1 F002 02361 Fault 1 Phase C Voltage Magnitude 0 to 999999.999 V 0.001 F060 02363 Fault 1 Phase C Voltage Angle -359.9 to 0 degrees 0.1 F002 02364 Fault 1 Type 0 to 11 --- 1 F148 0 (NA)2365 Fault 1 Location based on Line length units (km or miles) -3276.7 to 3276.7 --- 0.1 F002 02366 ...Repeated for Fault 2238C ...Repeated for Fault 323B2 ...Repeated for Fault 423D8 ...Repeated for Fault 5Synchrocheck Actual Values (Read Only) (4 modules)2400 Synchrocheck 1 Delta Voltage -1000000000000 to1000000000000V 1 F060 02402 Synchrocheck 1 Delta Frequency 0 to 655.35 Hz 0.01 F001 02403 Synchrocheck 1 Delta Phase 0 to 359.9 degrees 0.1 F001 02404 ...Repeated for Synchrocheck 22408 ...Repeated for Synchrocheck 3240C ...Repeated for Synchrocheck 4Autoreclose Status (Read Only)2410 Autoreclose 1 Count 0 to 65535 --- 1 F001 0Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 modules)2620 Remote Double-Point Status Input 1 Device 1 to 32 --- 1 F001 12621 Remote Double-Point Status Input 1 Item 0 to 64 --- 1 F606 0 (None)2622 Remote Double-Point Status Input 1 Name 1 to 64 --- 1 F205 "RemDPS Ip 1"2628 Remote Double-Point Status Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)2629 ... Repeated for Double-Point Status Input 22632 ... Repeated for Double-Point Status Input 3263B ... Repeated for Double-Point Status Input 42644 ... Repeated for Double-Point Status Input 5IEC 61850 GGIO5 Configuration (Read/Write Setting Registers) (16 modules)26B0 IEC 61850 GGIO5 uinteger Input 1 Operand --- --- --- F612 026B1 IEC 61850 GGIO5 uinteger Input 2 Operand --- --- --- F612 026B2 IEC 61850 GGIO5 uinteger Input 3 Operand --- --- --- F612 026B3 IEC 61850 GGIO5 uinteger Input 4 Operand --- --- --- F612 026B4 IEC 61850 GGIO5 uinteger Input 5 Operand --- --- --- F612 026B5 IEC 61850 GGIO5 uinteger Input 6 Operand --- --- --- F612 026B6 IEC 61850 GGIO5 uinteger Input 7 Operand --- --- --- F612 026B7 IEC 61850 GGIO5 uinteger Input 8 Operand --- --- --- F612 026B8 IEC 61850 GGIO5 uinteger Input 9 Operand --- --- --- F612 0Table B–10: MODBUS MEMORY MAP (Sheet 7 of 59)ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT