P44x/EN ST/Hb6 Setting(ST) 4-74 MiCOM P40 Agile P442, P444Or “Custom” can be selected in the menu to set a different voltage pick-up for any optoinputs:The default mappings for each of the inputs are shown in section P44x/EN PL.4.3 Relay output contact mappingThe default mappings and conditioning for each of the relay output contacts are shown in thefollowing table (PSL are equivalent for 442/444):RelayContactN°P442 Relay P444 Relay1 TripA+B+C & Z1 [straight] TripA+B+C & Z1 [straight]2 Any Trip Phase A [straight] Any Trip Phase A [straight]3 Any Trip Phase B [straight] Any Trip Phase B [straight]4 Any Trip Phase C [straight] Any Trip Phase C [straight]5 Signal send (Dist. or DEF)[straight]Signal send (Dist. or DEF)[straight]6 Any Protection Start [straight] Any Protection Start [straight]7 Any Trip [straight] Any Trip [straight]8 General Alarm [straight] General Alarm [straight]9DEF A+B+C Trip + IN>1Trip+ IN>2Trip[straight]DEF A+B+C Trip + IN>1Trip+ IN>2Trip[straight]10Dist. Trip &AnyZone&DistUnb CR[straight]Dist. Trip &AnyZone&DistUnb CR[straight]11 Autoreclose lockout[straight]Autoreclose lockout[straight]12 Autoreclose 1P+3P cycle inprogress [straight]Autoreclose 1P+3P cycle inprogress [straight]