P44x/EN PL/Hb6 Programmable Logic(PL) 6-48 MiCOM 40 Agile P442, P444Ordinal English Text Description Source64 Opto Label 01 OPTO ISOLATOR 1Set to 1 when the opto input is energised for aminimum time: 7ms (48Vdc), 10ms (universal) to bevalidated by internal logicTo enable the selection of a setting group by statechange of the opto isolated logic inputs 1 and 2,disconnect Opto inputs 01 and 02 in the PSL (Optoinputs 01 and 02 must not be connected to any outputsignal)OPTO65 Opto Label 02 OPTO ISOLATOR 2Set to 1 when the opto input is energised for aminimum time: 7ms (48Vdc), 10ms (universal) to bevalidated by internal logicTo enable the selection of a setting group by statechange of the opto isolated logic inputs 1 and 2,disconnect Opto inputs 01 and 02 in the PSL (Optoinputs 01 and 02 must not be connected to any outputsignal)OPTO66 to 95 Opto Label 03 toOpto Label 32OPTO ISOLATOR 3 toOPTO ISOLATOR 32Set to 1 when the opto input is energised for aminimum time:7ms (48Vdc), 10ms (universal) to bevalidated by internal logicOPTO350 Out Of Step Start of an Out of Step Detection (1st cycle), The firstout of step cycle has been detected (Zlocus in/out withthe opposite R sign) & the « Out Of Step start » picks-upPSL (OUT)352 Out Of Step Conf Out of Step Confirmed (number of cycles reached) PSL (OUT)700 to763Output cond. 1 toOutput cond. 64Input to Relay Output Conditioner PSL367 PAP Pre Start PAP (specific application) Picks up by voltagedetectors (timer initiated)PSL (OUT)366 PAP Pres IN Residual current detected by PAP (specific application)functionPSL (OUT)363 PAP Start A Phase A Start with PAP (specific application) function PSL (OUT)364 PAP Start B Phase B Start with PAP (specific application) function PSL (OUT)365 PAP Start C Phase C Start with PAP (specific application) function PSL (OUT)1089 PAP TeleT. Heath PAP (specific application) Carrier Out of Service (DTtrip decision)PSL(IN)1088 PAP TeleTrip CR PAP (specific application) Carrier Receive forteletransmissionPSL(IN)1090 PAP Timer Block Timer Block for frozen every timer initiated with PAP(specific application) functionPSL(IN)359 PAP Trip A Trip A Phase decision from PAP (specific application)functionPSL (OUT)360 PAP Trip B Trip B Phase decision from PAP (specific application)functionPSL (OUT)361 PAP Trip C Trip C Phase decision from PAP (specific application)functionPSL (OUT)362 PAP Trip IN Trip decision from PAP (specific application) function(Ground Fault detected)PSL (OUT)269 Power Swing Power swing detected (3 single phase loop inside thequad & crossing the ∆R band in less than 5ms in a 50Hz network). Power swing is present either with out ofstep cycle or stable swing cycle.PSL (OUT)Distance175 Prot'n Disabled Protection is disabled and test mode enabled PSL (OUT)1480 to1543PubPres VIP 1 toPubPres VIP 64Publishing presence of virtual input 1 (to 64): indicatesvirtual input 1 (to 64) presence.PSL1353 to1415Quality VIP 1 toQuality VIP 64Validation of the virtual input 1 (to 64)(signal correct).PSL