Programmable Logic P44x/EN PL/Hb6MiCOM 40 Agile P442, P444 (PL) 6-49Ordinal English Text Description Source0 to 63 Relay Label 01 toRelay Label 64OUTPUT RELAY 1 toOUTPUT RELAY 64High level when a DDB cell (linked by PSL logic) is at1. State depends on the logic set in the PSL (MiCOMS1 Agile)These programmable relays are assigned in the defaultPSL, with the following logic conditions (see section1.8.2):- Pulse time-delay- Pick Up/Drop Off Time-delay- Dwell Time-delay- Pick Up Time-delay- Drop Off Time-delay- Latching- Straight (used in default PSL)RELAY1081 Reset All values Reset all values of CB monitoring (all counters andvalues are reset ('CB condition')PSL (IN) CBMonitoring1082 Reset Latches Reset all permanent alarms + LEDs and relays arelatchedPSl (IN)1080 Reset Lockout Reset all CB monitoring lockout (all counters andvalues are reset ('CB condition')PSL (IN) CBMonitoring1091 Reset Thermal Reset Thermal Overload Protection PSL(IN)270 Reversal Guard Current reversal guard logic in action(Directional switching from Rev to Fwd in parallel lineapplication)PSL (OUT)Distance1112 RP1 Read Only All setting changes and most command/control actionsblocked for Rear Port 1.PSL1113 RP2 Read Only All setting changes and most command/control actionsblocked for Rear Port 2.PSL351 S. Swing Start of Stable Swing (1st cycle): The first stable swingcycle has been detected (Zlocus in/out with the sameR sign) & the « Stable Swing start » picks-upPSL (OUT)353 S. Swing Conf Stable Swing confirmed (number of cycles reached) PSL (OUT)437 SBO Closed Org 1 Select Before Operate (SBO) closing function fororgan 1 (interlocking facility in the IEC 60870-5-103protocol)PSL438 SBO Closed Org 2 Select Before Operate (SBO) closing function for organ2 (interlocking facility in the IEC 60870-5-103 protocol)PSL439 SBO Closed Org 3 Select Before Operate (SBO) closing function for organ3 (interlocking facility in the IEC 60870-5-103 protocol)PSL440 SBO Closed Org 4 Select Before Operate (SBO) closing function for organ4 (interlocking facility in the IEC 60870-5-103 protocol)PSL1118 SBO Command1 SBO support for IEC 61850-8-1 function command 1 PSL1122 SBO Command2 SBO support for IEC 61850-8-1 function command 2. PSL1126 SBO Command3 SBO support for IEC 61850-8-1 function command 3 PSL1130 SBO Command4 SBO support for IEC 61850-8-1 function command 4. PSL1116 SBO DPI1 Org1 SBO support for IEC 61850-8-1 function. SBO DoublePoint Information 1 Organe 1PSL1120 SBO DPI1 Org2 SBO support for IEC 61850-8-1 function. SBO DoublePoint Information 1 Organe 2PSL1124 SBO DPI1 Org3 SBO support for IEC 61850-8-1 function. SBO DoublePoint Information 1 Organe 3PSL1128 SBO DPI1 Org4 SBO support for IEC 61850-8-1 function. SBO DoublePoint Information 1 Organe 4PSL1117 SBO DPI2 Org1 SBO support for IEC 61850-8-1 function SBO DoublePoint Information 2 Organe 1PSL1121 SBO DPI2 Org2 SBO support for IEC 61850-8-1 function SBO DoublePoint Information 2 Organe 2PSL