Setting P44x/EN ST/Hb6MiCOM P40 Agile P442, P444 (ST) 4-15Menu text Default setting Setting range Step sizeMin MaxGROUP 1 – DISTANCE ELEMENTSRpG 25/In Ω 0 400/In Ω 0.01/In ΩRpG: Resistive reach – Earth fault element for zone P.RpPh 25/In Ω 0 400/In Ω 0.01/In ΩRpPh: Resistive reach – phase fault element for zone p.tZp 0.4s 0 10s 0.01sZone P time delay (TZp)Zone Q – Direct Directional Fwd Directional Fwd or Directional RevZone q is a further distance zone. It can be faster or slower than any other zone (exceptzone 1), and it can be in either direction. The only constraint is that it must be inside theoverall Z3/Z4 start-up zone.KZq Res Comp) 1 0 7 0.001KZq Angle 0° -180° 180° 0.1°Zone Q compensation (KZq residual compensation and kZq angle).Zq 27*V1/I1 0.001*V1/I1 500*V1/I1 0.001*V1/I1RqG 27*V1/I1 0 400*V1/I1 0.01*V1/I1RqG: Resistive reach – Earth fault element for zone Q.RqPh 27*V1/I1 0 400*V1/I1 0.01*V1/I1RqPh: Resistive reach – phase fault element for zone Q.tZq 0.5s 0 10s 0.01sZone Q time delay (TZq)