P44x/EN PL/Hb6 Programmable Logic(PL) 6-30 MiCOM 40 Agile P442, P444Ordinal English Text Description Source1544 to2047-- Unused (except next DDBs for specific options) PSL1672 to1677LN1 Analog AlarmtoLN6 Analog AlarmRelays with IEC 61850 9-2 Ethernet board only(software version D5.x)If two consecutive of any Logical Node frames have notbeen received within the Merge Unit Delay setparameter (time of silence in the reception of the frame),the LN is “absent”PSL1680 to1685LN1 Test Mode toLN6 Test ModeRelays with IEC 61850 9-2 Ethernet board only(software version D5.x)Any Logical Node is in “Test Mode”PSL1688 to1693LN1 Async toLN6 AsyncRelays with IEC 61850 9-2 Ethernet board only(software version D5.x)Any Logical Node is synchronized with Internal (local)synchronizationPSL1696 to1701LN1 Val Quest toLN6 Val QuestRelays with IEC 61850 9-2 Ethernet board only(software version D5.x)The sample value (SV) transmitted status from the LN is“questionable”PSL1704 to1709LN1 Val Fail toLN6 Val FailRelays with IEC 61850 9-2 Ethernet board only(software version D5.x)The sample value (SV) transmitted status from the LN is“failed”PSL1.1.2 Sorted by nameOrdinal English Text Description Source1111 103 CommandBlock For IEC-870-5-103 protocol only, used for "CommandBlocking" (relay ignores SCADA commands)PSL1110 103 MontorBlock For IEC-870-5-103 protocol only, used for "MonitorBlocking" (relay is quiet - issues no messages viaSCADA port)PSL328 1P Trip Single pole trip (internal or external) PSL (OUT)All protection318 1ph Fault Single phase fault PSL (OUT)Distance319 2ph Fault Two phase fault PSL (OUT)Distance329 3P Trip Three pole trip (internal or external) PSL (OUT)All protection320 3ph Fault Three phase fault PSL (OUT)Distance224 A/R 1P In Prog One-pole autoreclose cycle in progress: A single poleautoreclose cycle is in progress. This output will remainactivated from the initial protection trip until the circuitbreaker is closed successfully or the autoreclosefunction is Locked Out, indicating that a dead timetimeout is in progress. This signal may be useful duringrelay commissioning to check the operation of theautoreclose cycle.PSL (OUT)Autorecloser226 A/R 1st In Prog First high speed autoreclose cycle in progress: Used toindicate the autorecloser is timing out its first deadtime, either a high-speed single-pole shot or a highspeed three-pole shot.PSL (OUT)Autorecloser