21The requirements for Site Initiated AutoDownloading are as follows:1. Download Computer running PCPreset.2. Program the telephone number of theDownload Computer in location [90]Callback Telephone Number.3. Program location [93] with the number ofthe PCPreset account that is to bedownloaded.PCPreset1. Create the GEM-P801 account to bedownloaded using PCD-WindowsQuickloader Software.1. Create a List using PCPreset.2. Select the account by pressing t.Select the desired account from the list ofPCD3000 accounts available. (Thelocation in the list is the Auto DownloadID Number [93])3. Tag the list by entering aD ( download)4. Enter Standby Mode by entering o.The Computer is now in STANDBYSiteAt the site perform the following three steps:1. Arm the panel.2. Disarm the panel.3. Enter A6. The panel will nowcall the download computer runningPCPreset. PCPreset will answer the call,establish a connection, and thendownload the account that matches theAuto Download ID Number [93] with theaccount of the same number in the listthat PCPreset is currently running.Dealer Programming[94]Dealer CodeThe default Dealer Code is 4567. Programa new 4-digit Dealer Code. When the panelis defaulted the Dealer Code will bechanged back to the default Dealer Code of4567 only if Dealer Code Lockout [96-1]has not been programmed.[95]User 1 CodeThe 1st User code is a program code aswell as an Arm/Disarm code. The defaultUser Code is 1234. If User 1 CodeLockout is programmed the User 1 Codecannot be programmed from User ProgramMode.[96]Dealer Options 1(1) Dealer Code Lockout - Program toprevent the Dealer Code from changingwith a panel default.(2) User 1 Code Lockout - If programmedthe User 1 Code cannot be programmedfrom User Program Mode.(3) Household Fire - Activates thefollowing UL required features:There is a 4 hour re-sound of wirelessSmoke Low Battery and wireless SmokeSupervisory system troubles.• An active System Battery test performedevery 4 hours instead of 24 hours andWireless Smoke Supervisory Timer is setto 4 hours.• Fire Bell Timing is March Time.• Wireless Smoke Supervisory Time isfixed at 4 hours.(4) Fire Trouble on Fire LED - Normally alltroubles are displayed on the HSYSTEMTROUBLE LED, including Fire Trouble. Ifrequired Fire Trouble can be displayed on theFire LED. Fire Trouble is indicated by asteady IFire LED.[97]Dealer Options 2(1) International Dialing Protocol - Nodialing if no dial tone, 60 s between attemptsand 4 s wait for dial tone.(2) Invert Bell Output - Inverts the Bellpolarity and removes supervision from thebell circuit.(3) System Trouble Auto Restore -Normally, System troubles requireacknowledgment (View System Trouble) inorder to restore. If this option is selectedtroubles will restore without requiringacknowledgment.(4) User 1 Code-Program only - If enabledUser 1 Code will function only as the UserProgram Code and will not Arm/Disarm thepanel.