7Burglary Zone WiringThe GEM-P801 provides 6 true hard-wired, End-Of-Line Resistor terminated burglary zones. Wirezones as shown in the wiring diagram (pg. 27).All resistors must be installed, even if the zone isnot used. If required, the feature No End Of LineResistor may be programmed, in which case adirect short across the zone will cause the zoneto set up. (NOTE: Not for UL applications)Program the zone as a No EOL Resistor Zone[06].If necessary, use the voltage chart below to verifyproper voltages. These values represent the DCvoltage of the zone while in the indicated statewith reference to the the zone’s respectiveground terminal.Fire Zone WiringWire the Fire Zone as shown in the WiringDiagram in the back of this manual. An EOLresistor must be installed, even if the Fire Zoneis not used.PGM WiringThe PGM (Terminal 19) is a switched negativeoutput that is activated through programmingoption(s) that have been selected inprogramming blocks [08], [23] - [25], [26-2].Connect the device controlled by the PGMbetween +PWR and the PGM terminal.(maximum load of 50 mA).Keypad OperationKeypad zone LEDs indicate zone status.ARMED, STATUS and HSYSTEM LEDsprovide system status. The keypad sounderprovides feedback beeps for correct andincorrect entries.Keypad Sounder3 QUICK BEEPSPanel Armed (System ON)Chime ONFault Find Mode ONKeypad Sounder ONZone Bypassed6 QUICK BEEPSPanel Disarmed (System OFF)Chime OFFFault Find Mode OFFKeypad Sounder OFFZone Un-Bypassed1 SECOND - STEADY TONEIncorrect Code EnteredInvalid key entry4 LONG BEEPS (PRIORITY CONDITION)1. Entering an Arm Code with a faulted zone(Not an Auto-Bypass Reentry Zone).2. Entering an Arm Code when the Bell orPGM is ON (Bell and PGM will turn OFF).3. Arming with the Fire LED ON - resetrequired. Press the C key.Fire Zone Normal 13.0VFire Trouble 13.8VFire 0.0 VTABLE 4 V OLTAGE AT F IRE Z ONE (Terminals 12&13)Zone Normal (EOL across zone) 2.5 VZone shorted 0 VZone Open 5 VTABLE 3 V OLTAGE AT T ERMINALS 3&5, 6&8, 9&11