59With LF.3 you disable the direction input to prevent the drive fromresponding. This allows the drive the measure the motor resistance orthe alignment of the encoder on a PM motor by running the car oninspection.Value range: runrunrunrunrun ... conFconFconFconFconF ... EconFEconFEconFEconFEconFFactory setting: conFconFconFconFconFDrive ConfigurationParameter Description - Basic Set UpThis parameter is time limited for safety. Once conFconFconFconFconF isactivated you have 5 minutes to complete the alignmentor measurement process. After the timer runs out, themode will change to EconFEconFEconFEconFEconF (expired configuration mode).It will be necessary to change back to conFconFconFconFconF thus resettingthe timer to continue. Once all set up is complete set thisparameter to runrunrunrunrun.This parameter displays the current mode of operation, open or closedloop, geared or gearless, induction motor, synchronous motor. Theparameter is read only.Possible displays:IOPEn = Open loop inductionICLSd = Closed loop inductionI9LSS = Closed loop induction gearlessPCLSd = Closed loop permanent magnetP9LSS = Closed loop permanent magnet gearlessWith LF. 5 all drive faults can be automatically reset.The number adjusted in this parameter determines how many timesper hour the elevator drive will automatically reset faults. Beforeresetting the fault, the drive will wait 4 seconds to allow everything tostop or stabilize. It is not fault specific, so with the default setting of 3,if the drive experiences 4 different faults in one hour the unit will latchthe last fault and not reset. See parameter LF.98 for fault historyinformation.Unit: 1Value range: 0...10Factory setting: 3Drive Fault Auto ResetMotor-SelectionNote: a setting of “0”means no fault resets.i