Appendix F: Type Codes Type Codes for Output Devices106 NFS-640 Programming Manual P/N 51333:B 10/03/2003Type Codes for Output DevicesOverviewThis section provides Type Codes for control modules, NACs, and Panel Circuits. For instructions onprogramming Type Codes, refer to “How to Modify or Delete a Point (2=point)” on page 21.Type Codes for Control ModulesA comprehensive list of control module Type Codes, which you can select to change the function of ancontrol module point.Table 34 Control Module Type CodesType Code Silenceable(Y/N) Configuration Device FunctionCONTROL Y NAC Supervised NAC for notification applianceRELAY Y Form-C relay Relay outputBELL CIRCUIT Y NAC Supervised NAC for notification applianceSTROBE CKT Y NAC Supervised NAC for notification applianceHORN CIRCUIT Y NAC Supervised NAC for notification applianceAUDIBLE CKT Y NAC Supervised NAC for notification applianceSPEAKER Y NAC Supervised NAC for notification applianceISOLATED NAC Y NAC Supervised NAC for notification appliance, used with audio isolators. Activateseven if there is a short on its NAC circuit. For ULC installations only.ISOLATED SPK Y NAC Supervised NAC for speaker circuits, used with audio isolators. Activates even ifthere is a short on its audio circuit. For ULC installations only.REL END BELL N NAC Supervised NAC for notification applianceblank Y NAC Supervised NAC (for use when no other Type Code applies)REL CKT ULC N NAC Releasing Circuit, power-limited, supervised for opens, shorts and ground faults(always non-silenceable)RELEASE CKT N NAC Releasing circuit, nonpower-limited, supervised for opens and ground faultsRELEA.FORM C N Form-C Relay Relay output, contacts operate upon releaseREL AUDIBLE Y NAC NAC, activated upon releaseNONRESET CTL N Form-C Relay and NAC Relay output, unaffected by “System Reset” commandTELEPHONE N NAC Standard Telephone circuitINSTANT RELE N NAC NAC, short = normal; supervised for open circuits and ground faults. Always non-silenceable and switch-inhibited.ALARMS PEND. N NAC Output that will activate upon receipt of an alarm condition, and remain in thealarm state until all alarms have been acknowledged. It is programmed as “switchinhibit”.CONTROL NAC Y NAC Supervised NACGEN ALARM N NAC Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) configured as aMunicipal Box Transmitter for NFPA 72-1999 Auxiliary Fire Alarm Systemsapplications. This Type ID can also be used for general alarm activation. It isprogrammed as “switch inhibit”.GEN SUPERVIS N NAC Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated under anySupervisory condition (includes sprinkler type). It is programmed as “switch inhibit”.GEN TROUBLE N NAC Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated under anySystem Trouble condition. It is programmed as “switch inhibit”.GENERAL PEND N NAC Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will activateupon receipt of an alarm and/or trouble condition, and remain in the ON state untilall events have been ACKNOWLEDGED.TROUBLE PEND N NAC Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that will activateupon receipt of a trouble condition, and remain in the ON state until all troubleshave been ACKNOWLEDGED. It is programmed as “switch inhibit”.www.PDF-Zoo.com