How to Use the Basic Program 2. Program ChangeNFS-640 Programming Manual P/N 51333:B 10/03/2003 29How to Program Special Zones (6=SPL FUNCT)The Special Zone Change option lets you change the program for Special ZonesF0-F9 or Releasing Zones R0-R9. From the “Basic Program” screen, press the6 key to display the “Special Function Change” screen as shown below:.What are Special Zones?Descriptions for each Special Zone that appears in the “Special Function Change” screen are detailedbelow:Note: Special Zones F0-F9 appear in the CBE list of device as ZF0-ZF9. For example, if you list F0 for a detector, oneof the five zones in the CBE list of the detector will display as ZF0.Table 9 Summary of Special ZonesThe control panel also provides four Special Zones, F1-F4, which are outputs that do not appear on theSpecial Function Change screen. You can program Special Zones F1 to F4 into the CBE of an outputdevice. Descriptions of F1, F2, F3, and F4 are detailed below:Note: To view the status of Special Functions F1-F4, use the Read Status function (refer to the NFS-640 OperationsManual).Table 10 Special Output Functions F1-F4Special Zone Lets youF0=PRESIG Select a Presignal Delay Timer and select PAS (Positive AlarmSequence)F5-F6= TIME Specify Time Control functions such as the start time, stop time,or days of the weekF7=HOL Specify up to nine holiday dates. An F7-programmed deviceactivates on the specified holiday datesF8=CODE Specify one of seven coding function selections: March Time,Temporal, California, Two-Stage, Canadian Two-Stage (3minute or 5 minute), or System Sensor Strobes. F8 only takeseffect if you program one or more NACs to F8F9=PRE- ALARM Select a Pre-Alarm level: Alert or ActionR0-R9= REL Program up to ten Releasing Zones, each with a selection for aDelay Timer, an Abort Switch, a Cross Zone selection, or a SoakTimerSpecial Function SpecifiesF1 (Trouble less AC) An output programmed to turn on/off if a system trouble—otherthan an AC power loss—occursF2 (AC Trouble) An output programmed to turn on/off if an AC power loss or abrownout condition occursF3 (Security) An output programmed to turn on/off if a Security inputactivatesF4 (Supervisory) An output programmed to turn on/off if a Supervisory inputactivatesProgram ChangePasswordSPECIAL FUNCTION: F0=PRESIG R0-R9=RELF5-F6=TIME F7=HOL F8=CODE F9=PRE-ALARMwww.PDF-Zoo.com