How to Disable or Enable a Point 3. Status ChangeNFS-640 Programming Manual P/N 51333:B 10/03/2003 47How to Disable or Enable a PointThe Disable/Enable option lets you disable programmed points for detectors,modules, zones, and NACs and Panel Circuits. The program allows you to disablean initiating device in alarm: however, the disable will not take effect until afterthe panel has been reset.1. From the “Status Change Selection” screen, press the 1 key to display the “Disable/Enable” screen.2. Select the point type:for detectorsfor modulesfor NAC and Panel Circuitsfor zonesThe cursor will blink the first SLC address digit in the detector, zone, module, or NAC/Panel Circuitfield.WARNING: Disabling a zone disables all input and output devices that use the zone as the firstentry in the CBE list.3. Enter the address of the point, then press the ENTER key. A sample display follows:When you disable a point and press the ESC key to return to the Disable/Enable screen, the controlpanel: a) turns on the POINT DISABLED LED; b) sounds the panel sounder; and c) changes the statusbanner to TROUBL for the point.You can disable or enable a point by changing the status banner as follows:To PressChange the status Maneuver the cursor with the arrow keys until it is inthe status field. Press(Next Selection) or (Previous Selection)Save the statusGo to the next orprevious point address (Next Selection) or (Previous Selection)Status ChangePasswordENABLE CONTROL CONTROL ADDRESS 2M10100 __ __ __ __ ISW 2M101Blinking status banner (ENABLE or DISABL)www.PDF-Zoo.com