Type Codes for Output Devices Appendix F: Type CodesNFS-640 Programming Manual P/N 51333:B 10/03/2003 107NAC and Panel Circuit Type CodesA comprehensive list of Type Codes for panel NACs and Panel Circuits. The Type Codes that display,however, depend on the type of circuit: NAC or Panel Circuit relay. For instructions on programmingType Codes, refer to “How to Modify or Delete a Point (2=point)” on page 21.Note: Do not assign Releasing Type Codes to Panel Circuits with the exception of the audible Type Codes REL ENDBELL and REL AUDIBLE.Table 35 NAC and Panel Circuit Type CodesType Code Silenceable(Y/N) Configuration Device FunctionCONTROL Y Panel Circuit relay or NAC Supervised NACRELAY Y Panel Circuit relay Relay outputBELL CIRCUIT Y Panel Circuit relay or NAC Supervised NAC for notification applianceSTROBE CKT Y Panel Circuit relay or NAC Supervised NAC for notification applianceHORN CIRCUIT Y Panel Circuit relay or NAC Supervised NAC for notification applianceAUDIBLE CKT Y Panel Circuit relay or NAC Supervised NAC for notification applianceSPEAKER N Panel Circuit relay only Supervised NAC for speaker circuitsREL END BELL N Panel Circuit or NAC Supervised NACblank label Y Panel Circuit relay or NAC Supervised NAC for undefined deviceREL CKT ULC N NAC Releasing Circuit, power-limited, supervised for opens, shorts and groundfaults (always non-silenceable)RELEASE CKT N NAC Releasing circuit, nonpower-limited, supervised for opens and ground faultsREL AUDIBLE Y Panel Circuit or NAC NAC, activated upon releaseTELEPHONE N Panel Circuit relay only Standard Telephone circuitREL CODEBELLY NAC only Supervised NAC (NFS-640 NAC only)INSTANT RELE N NAC NAC, short = normal; supervised for open circuits and ground faults. Alwaysnon-silenceable and switch-inhibited.ALARMS PEND N Panel Circuit or NAC Output that will activate upon receipt of an alarm condition, and remain in thealarm state until all alarms have been acknowledged. It is programmed as “switchinhibit”.CONTROL NAC Y Panel Circuit relay or NAC Supervised NACGEN ALARM N NAC Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) configured as aMunicipal Box Transmitter for NFPA 72-1999 Auxiliary Fire Alarm Systemsapplications (MBT-1 required). This Type ID can also be used for general alarmactivation. It is programmed as “switch inhibit”.GEN SUPERVIS N NAC Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated underany Supervisory condition (includes sprinkler type). It is programmed as “switchinhibit”.GEN TROUBLE N NAC Control Module, an XPR-8 relay, or an XP5-C (in relay mode) activated underany System Trouble condition. It is programmed as “switch inhibit”.GENERALPENDN NAC Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that willactivate upon receipt of an alarm and/or trouble condition, and remain in theON state until all events have been ACKNOWLEDGED.TROUBLE PEND N NAC Control Module, an XPC-8 circuit, or an XP5-C (in NAC mode) that willactivate upon receipt of a trouble condition, and remain in the ON state until alltroubles have been ACKNOWLEDGED. It is programmed as “switch inhibit”.www.PDF-Zoo.com