46 NFS-640 Programming Manual P/N 51333:B 10/03/20033. Status ChangeWhat is Status Change?Status Change provides a second programming level - accessed by an assigned password - for changingoperating parameters. (These operating parameters do not affect control program settings.) For example,the Status Change password lets you change settings such as: detector sensitivity, system time and date,and so on.Note: Assign the Status Change password to persons who do not have access to Level 1 programming options.How to Enter Status ChangeTo enter Status Change, follow these steps:1.From the SYSTEM NORMAL” screen, press the E NTER key. The control panel displays the “Entry”screen, as shown below:2.From the “Entry” screen, press the 1 key. The control panel displays the “Enter Password” screen asshown below:3.Enter your Status Change password (See “How to Enter a Password”, page 13). The control paneldisplays the “Status Change Selection” screen, as shown below:4.Select a Status Change selection: 1,2,3,4,5, or 6.Status Change OptionsOption 1=DISABL - The Disable/Enable option lets you disable programmed points for detectors,modules, zones and NAC/Panel Circuit modules. For details, refer to “How to Disable or Enable aPoint” on page 47.Option 2=SENSITIV - The Detector Sensitivity option lets you change the Alarm and Pre-alarm(sensitivity) level for an installed detector. For details, refer to “How to Change Sensitivity for aDetector” on page 48.Option 3=CLR VER - The Clear Verification screen lets you clear all counters for detectors selectedfor Alarm Verification. For details, refer to “How to Clear Alarm Verification Counters” on page 49.Option 4=CLR HIST - The Clear History screen lets you clear the entire History buffer from memory.For details, refer to “How to Clear the History Buffer” on page 49.Option 5=TIME - The Time/Date option lets you set the time and date for the system clock. For details,refer to “How to Set the System Time and Date” on page 49.Option 6=WALK TEST - The Walk Test option lets you test the entire fire alarm system while awayfrom the control panel. For details, refer to “How to Do a Walk Test” on page 50”.1=PROGRAMMING 2=READ STATUS ENTRYENTER PROG OR STAT PASSWORD, THEN ENTER.STATUS CHANGE PRESS: 1=DISABL 2=SENSITIV3=CLR VER 4=CLR HIST 5=TIME 6=WALK TESTwww.PDF-Zoo.com