How to Use the Basic Program 2. Program ChangeNFS-640 Programming Manual P/N 51333:B 10/03/2003 17Create a New Program for the Control PanelThis section covers how to use the Autoprogram option to create a new programfor the control panel. The control panel will identify all addressable detectors andmodules connected to the SLC.To create a new program for the control panel, follow these steps:1. Use the Clear option to clear program information from memory. For instructions on clearingmemory, refer to “How to Clear Memory (0=CLR )” on page 16.2. From the “Basic Program” screen, press the 1 key to start Autoprogram. While the control panelscans the system to identify all SLC devices, Panel Circuits and NACs, it displays the followingscreen:When the autoprogram is finished identifying SLC devices, Panel Circuits and NACs, it displays asummary screen that gives a count of all the devices it has located. Refer to the following screen foran example of this display.3. Press ENTER . All devices are automatically accepted during initial autoprogramming. Thefollowing screen displays briefly, followed by the SYSTEM NORMAL screen.To edit the autoprogramming default values for a point, refer to”How to Modify or Delete a Point(2= POINT )” on page 21.To edit the autoprogram default values assigned to all modules and detectors during autoprogramming,refer to “How to Change Autoprogram Default Values” on page 20.Program ChangePasswordAUTOPROGRAM PLEASE WAITL1:010Dets, 159Mods L2:159Dets, 159ModsPanel Outputs: 64 Bells: 04ACCEPT ALL DEVICES Please Wait!!!www.PDF-Zoo.com