KW2G/ KW2G-H Eco-POWER METER38++++Current alarm setting mode *It is only when ‘AL-C’ is selected on unit for pulse output setting mode.Mode defines the ratio of current used for alarm output. (Ratio for the rated current)・It is set the range of 0.1 to 100.0%.Set it using - △>,+
- △>.(0.1 to 100.0) IncreaseDecrease↓Stand-by alarm setting mode 1 *It is only when ‘AL-S’ is selected on unit for pulse output setting mode.Mode defines the ratio of current used for threshold value to judge stand-by power.(Ratio for the rated current)・It is set the range of 0.1 to 100.0%.Set it using
- △>,+
- △>.(0.1 to 100.0) IncreaseDecrease↓Stand-by alarm setting mode 2 *It is only when ‘AL-S’ is selected on unit for pulse output setting mode.Mode defines the time used for threshold value to judge stand-by power.・It is set the range of 0 to 9999min.When ‘0’ is set, alarm is always output at the time when judging the stand-by power.When ‘1 to 9999’ is set, alarm is output at the time when passing the setting time with the stand-bypower.The alarm can be reset by pressing with the instantaneous electric power display. Afterreset the alarm, start to monitor the stand-by power again.Set it using
- △>,+
- △>.( 0 to 9999 min.) IncreaseDecrease↓Preset value setting mode *It is only when ‘Cnt’ is selected on unit for pulse output setting mode.Mode defines count value used for output.・It is set the range of 0(0.000) to 999999(999.999).*The range differs according to the pre-scale set by pre-scale setting mode.Set it using
- △>,+