KW2G-H Eco-POWER METER57(4)(1)(2)(3)(1) Device information (Row 1) Logging data number(Row 2) KW2G Model name(Row 3) COM1[Unit No.01 No.1]Station number(based on the unit setting)(Row 4) DT120 Target address (only the beginning)(Row 5) DIFFERENCE Shows ‘difference value’(Row 6) US32 -> FLT Unsigned integer 32 bit(Row 7) kWh Unit (based on the target address)(2) Logging trigger Timing to log data: 15 minutes fixed (00,15,30,45 of each hour)(3) Record number Record number for 1 file: 96 records fixedTiming of creating file: 00:00:00 every day(4) Logging data ・Record in 1 file regardless f the type・‘-’ is recorded for immeasurable itemsLogging data of the same timing: 5 data (fixed)From column C to GIntegrated electric power(1), Integrated electric power(2), Count valueCH0 pulse count value, CH1 pulse count value*In case of no data is the past, it will record ‘0’.*‘Integrated electric power’ is logged with the unit of 0.01kWh.It doesn’t log it with the unit of 0.001kWh.A B C D E F G H1 Date Time 1 2 3 4 5 62 KW2G KW2G KW2G KW2G KW2G3 COM1[Unit No.01] COM1[Unit No.01] COM1[Unit COM1[Unit COM1[Unit No.01]4 DT100 DT122 DT154 DT194 DT1965 DIFFERENCE DIFFERENCE DIFFERENDIFFERENDIFFERENCE6 US32 ->FLT US32 ->FLT US32 ->FLUS32 ->FLUS32 ->FLT7 kWh kWh CNT pulse pulse8 2012/4/1 0:00:009 2012/4/1 0:15:0010 2012/4/1 0:30:00