KW9M Eco-POWER METER365.1.7 Current・The present current value is displayed.・It measures from 0.1% of CT secondary current.・When input current exceeds 200% or the display range, it displays “- - - - -“.・Current measuring pointsEco-POWER METER measures the current as below.Display 1P2W 1P3W 3P3W3P4W1 1st circuit R-current R-current R-current2 2nd circuit R-current N-current S-current3 3rd circuit R-current T-current T-current5.1.8 Voltage・The present voltage is displayed.・Press ▽> to change phase voltage and line voltage.(Line voltage is not displayed for 1P2W system. Phase voltage is not displayed for 3P3W system.Phase voltage Line voltage・When input voltage is under 3V (when VT ratio is 1.), it displays “0.0” and doesn’t measure.・When input voltage exceeds 600V or the display range, it displays “- - - - -“.・Voltage measuring pointsEco-POWER METER measures the voltage as below.Display 1P2W 1P3W 3P3W 3P4W1 R-voltage (L1-N)or 1st circuit R-voltage R-voltage (L1-N) R-voltage (L1-N)2 None or2nd circuit R-voltage None S-voltage (L2-N)3 None or3rd circuit R-voltage T-voltage (L3-N)No displayT-voltage (L3-N)1 2 R-voltage (L1-N) RS-voltage (L1-L2) RS-voltage (L1-L2)2 3 T-voltage (L3-N) ST-voltage (L2-L3) ST-voltage (L2-L3)3 1No displayTR-voltage (L3-L1) TR-voltage (L3-L1) TR-voltage (L3-L1)