KW9M Eco-POWER METER47◆[MD]: Register or Reset data monitored (Registers the data to be monitored.) *Up to 16 points can be registered for one unit.◇Command (Register) Data specification ① Data specification%×10 1 ×10 0# M D D×104 ×10 3 ×102 ×10 1 ×100D×10 4 ×103 ×10 2 ×10 1 ×10 0 ×16 1 ×16 0CR◇Command (Register reset)%×10 1 ×10 0# M D F F F F F F×16 1 ×160CR◇Normal response (Registration successful)%×10 1 ×10 0$ M D×16 1 ×160CR◆[MG]: Monitoring start (Monitors a registered data.)◇Command%×10 1 ×10 0# M G×16 1 ×160CR◇Normal response (Monitoring successful)%×10 1 ×10 0$ M G 0 0 0×161 ×16 0 ×161 ×16 0 ×163 ×16 2 ×16 1 ×16 0 ×16 3 ×16 2 ×16 1 ×16 0CR◆[RT]: Read the status of Eco-POWER METER (Reads the specifications of Eco-POWER METER and error codes if an error occurs.)◇Command%×10 1 ×10 0# R T×16 1 ×160CR◇Normal response (Read successful)%×10 1 ×10 0$ R T×16 1 ×160 ×16 1 ×160 ×16 3 ×162 ×16 1 ×160 ×16 1 ×160 ×16 1 ×16 0 ×16 1 ×16 0 ×16 3 ×16 2 ×16 1 ×16 0CR*With this unit, it responses "99" for Model code1, "16" for Model code2.Word No.5 charactersWord No.5 characters BccDestinationBccFixed (6 characters)Source BCCDestination BccSourceDestination BccSource Model code 12 charactersModel code 22 charactersBccData ①4 charactersNo. of charactersin data lin e2 charactersData4 charactersNo. of charactersBccVersion4 charactersSelf-diagnostic error No.4 charactersOperation mo de2 cha racters Error flag2 characters(lower word) (higher word)(lower word) (higher word)nn16 points max.(lower word) (higher word)Operation mode01: On operating00: StopError flag01: abnormal00: normalDestinationNote) The maximum number of reading slaves is 26 (57 bytes), the maximum number of writingslaves is 23 (55 bytes).