KW9M Eco-POWER METER50<3> Reset integral active power (0064H, 0065H: 2-word) of address 1(When setting to 0 [0000, 0000H])・Command3.5 idlecharactersSlaveaddress(01H)Functioncode(10H)Data item(0064H)Number ofdata item towrite(0002H)Number ofdata(04H) ⇒1 1 2 2 1 ←characternumber⇒ Data 1(0000H)Data 2(0000H)Error checkCRC-16(F474H)3.5 idlecharacters2 2 2 ←characternumber・Response message from slave in normal status3.5 idlecharactersSlaveaddress(01H)Functioncode(10H)Data item(0064H)Number ofdata item towrite(0002H)Error checkCRC-16(0017H)3.5 idlecharacters1 1 2 2 2 ←characternumber・A response message from the slave in exception (error) status(When number of data has been mistaken.)Function code MSB is set to 1 for the response message in exception (error) status (90H).The exception code 03H (Value out of the devise numbers) is returned as contents of error.3.5 idlecharactersSlaveaddress(01H)Functioncode(10H)Number ofdata item towrite(0002H)Number ofdata(06H) ⇒↑Mistake⇒ Data 1(0000H)Data 2(0000H)Error checkCRC-16(8F8E)3.5 idlecharacters(Response message in exception (error) status)>3.5 idlecharactersSlaveaddress(01H)Functioncode(90H)Exception code(03H)Error checkCRC-16(0C01H)3.5 idlecharacters