3.5 Wiring MECHATROLINK-II Communications3-273 Wiring and Connection3.5 Wiring MECHATROLINK-II CommunicationsThe following diagram shows an example of connections between a host controller and a SERVOPACK usingMECHATROLINK-II communications cables (CN6A, CN6B).Note 1. The length of the cable between stations (L1, L2 ... Ln) must be 0.5 m or more.2. The total cable length must be L1 + L2 ... + Ln ≤ 50.3. When multiple SERVOPACKs are connected by MECHATROLINK-II communications cable, a terminator mustbe installed at the final SERVOPACK.LnL1L2TerminatorDC24VDC 0VMP2300YASKAWATESTޓޓޓOptionOptionRDYALMTXRUNERRBATMONCNFGINTSUPSTOPSW1OFF ONBATTERYCPU I/OM-I/II218IF-01ERRCOLRXRUNSTRXTXINITTESTONOFFPORT10Base-T