3 Wiring and Connection3.8.3 Connecting a Reactor for Harmonic Suppression3-36Connect the noise filter ground wire directly to the ground plate.Do not connect the noise filter ground wire to other ground wires.If a noise filter is located inside a control panel, first connect the noise filter ground wire and theground wires from other devices inside the control panel to the ground plate for the control panel,then ground the plates.3.8.3 Connecting a Reactor for Harmonic SuppressionThe SERVOPACK has reactor connection terminals for power supply harmonic suppression that can be usedas required. The reactor is an optional part. You must acquire it separately. For reactor selection and specifica-tions, refer to theΣ-V Series Product Catalog (Catalog No.: KAEP S800000 42).Connect a reactor as shown in the following diagram.Note 1. Connection terminals for DC reactor 1 and 2 are short-circuited at shipment. Remove the lead wire forshort-circuit, and connect a DC reactor.2. DC reactors cannot be connected to SERVOPACKs with a single-phase 100-V power input.Shieldedground wireNoiseFilterNoiseFilterSERVOPACK SERVOPACK SERVOPACK SERVOPACKGround plateGround plateIncorrect CorrectNoiseFilterControl PanelGroundSERVOPACKSERVOPACKGround plateSERVOPACK with 100-VAC Power Input SERVOPACK with 200/400-VAC Power InputL1L2SERVOPACKAC reactorPowersupply12SERVOPACKDC reactor