GUID-4AFE14A9-42C2-4527-95C7-6F7179896903 V1 ENFigure 20: Importing IED configuration2. In the Import dialog box, select the .pcmi file to be imported and click Open.After importing, the IED object is created in the plant structure.After the .pcmi file has been imported, the IP address, the name and the technical keythat correspond to the physical IED have to be changed.4.7 Setting the IED IP address in a projectThe IP address and subnet mask of the IED object in PCM600 must match the frontand rear port of the physical IED to which the PC is connected. The IP address of thephysical IED can only be set via the LHMI and cannot be set from PCM600. The PCand IED may need to be on the same subnet.In PCM600, there are two alternatives to set the IP address of an IED object.Section 4 1MRS240044-IB ASetting up a project44 REF615REngineering Manual