GUID-6F47B4AD-B956-4F77-A6A2-DE6F4A71D607 V1 ENFigure 31: Creating a new IED into the SAB600 project5. Check the default settings in the SCL Import view and change the settings ifthey are not suitable.The default settings in the SCL Import dialog should be OK in most cases.6. Click Import to import the SCD file.7. Check the IP address on the IEC61850 subnetwork and change it if needed.When the SCD file is direcly exported from PCM600, it will use the IP address ofthe PCM600 computer, not the COM600.The communication towards the IEDs is now ready. For information on how to finalizethe single-line diagram and enable parameter setting through COM600 HMI, see theCOM600 documentation.4.10 Using the Web HMITo establish a remote WHMI connection to the IED, contact thenetwork administrator to check the company rules for IP and remoteconnections.WHMI is enabled by default. Log in with the proper user rights to use the WHMI.Section 4 1MRS240044-IB ASetting up a project56 REF615REngineering Manual