Section 3 Configuration3.1 Introduction SEMOD120082-1 v1SEMOD172508-5 v6The IED is available to be ordered in four different alternatives with theconfiguration suitable for the application. Normally these configurations should beacceptable to use with only few changes of binary input and outputs, which can bedone from the signal matrix tool in the PCM600 engineering platform.The main protection functions are switched Off at delivery. Back-up functions notgenerally used are also set to Off.The configurations are:• Single-breaker arrangement. Three phase tripping arrangement for non directlyearthed systems.• Single-breaker arrangement. Three phase tripping arrangement.• Single-breaker arrangement. Single phase tripping arrangement.• Multi-breaker arrangement. Three phase tripping arrangement.• Multi-breaker arrangement. Single phase tripping arrangement.The Multi-breaker arrangement includes one-and-a-half breaker and ring-breakerarrangements.The number of IO must be ordered to the application where more IO is foreseen forthe single-phase tripping arrangements respectively the multi-breaker arrangement.The basic delivery includes one binary input module and one binary outputmodule, which is sufficient for the default configured IO to trip and close thecircuit breaker.However, all IEDs can be reconfigured with help of the application configurationtool, being part of the PCM600 platform. This way the IED can be made suitablefor special applications and special logic can be developed, such as logic forautomatic opening of disconnectors and closing of ring bays, automatic loadtransfer from one busbar to the other, and so on.1MRK 506 369-UEN B Section 3ConfigurationLine distance protection REL670 2.2 IEC 59Application manual