18.2.3 Setting guidelines GUID-DF6BEC98-F806-41CE-8C29-BEE9C88FC1FD v3The parameters for Gas medium supervision SSIMG can be set via local HMI orProtection and Control Manager PCM600.Operation: This is used to disable/enable the operation of gas medium supervisioni.e. Off/On.PresAlmLimit: This is used to set the limit for a pressure alarm condition in thecircuit breaker.PresLOLimit: This is used to set the limit for a pressure lockout condition in thecircuit breaker.TempAlarmLimit: This is used to set the limit for a temperature alarm condition inthe circuit breaker.TempLOLimit: This is used to set the limit for a temperature lockout condition inthe circuit breaker.tPressureAlarm: This is used to set the time delay for a pressure alarm indication,given in s.tPressureLO: This is used to set the time delay for a pressure lockout indication,given in s.tTempAlarm: This is used to set the time delay for a temperature alarm indication,given in s.tTempLockOut: This is used to set the time delay for a temperature lockoutindication, given in s.tResetPressAlm: This is used for the pressure alarm indication to reset after a settime delay in s.tResetPressLO: This is used for the pressure lockout indication to reset after a settime delay in s.tResetTempLO: This is used for the temperature lockout indication to reset after aset time delay in s.tResetTempAlm: This is used for the temperature alarm indication to reset after a settime delay in s.Section 18 1MRK 506 369-UEN BMonitoring776 Line distance protection REL670 2.2 IECApplication manual