Func103N: Function type number (0-255) for binary input N according toIEC-60870-5-103, that is, 128: Distance protection, 160: overcurrent protection,176: transformer differential protection and 192: line differential protection.Info103N: Information number (0-255) for binary input N according toIEC-60870-5-103, that is, 69-71: Trip L1-L3, 78-83: Zone 1-6.See also description in the chapter IEC 60870-5-103.18.6.3.3 Analog input signals M12179-92 v6Up to 40 analog signals can be selected among internal analog and analog inputsignals. PCM600 is used to configure the signals.For retrieving remote data from LDCM module, the Disturbancereport function should be connected to a 8 ms SMAI function blockif this is the only intended use for the remote data.The analog trigger of Disturbance report is not affected if analog input M is to beincluded in the disturbance recording or not (OperationM = On/Off).If OperationM = Off, no waveform (samples) will be recorded and reported ingraph. However, Trip value, pre-fault and fault value will be recorded and reported.The input channel can still be used to trig the disturbance recorder.If OperationM = On, waveform (samples) will also be recorded and reported ingraph.NomValueM: Nominal value for input M.OverTrigOpM, UnderTrigOpM: Over or Under trig operation, Disturbance reportmay trig for high/low level of analog input M (On) or not (Off).OverTrigLeM, UnderTrigLeM: Over or under trig level, Trig high/low level relativenominal value for analog input M in percent of nominal value.18.6.3.4 Sub-function parameters M12179-389 v3All functions are in operation as long as Disturbance report is in operation.Indications M12179-448 v4IndicationMaN: Indication mask for binary input N. If set (Show), a status changeof that particular input, will be fetched and shown in the disturbance summary onlocal HMI. If not set (Hide), status change will not be indicated.SetLEDN: Set red LED on local HMI in front of the IED if binary input N changesstatus.1MRK 506 369-UEN B Section 18MonitoringLine distance protection REL670 2.2 IEC 789Application manual